background image

Manual 2100-764 
Page 

6 of 8

“Y1” Potentiometer setting:

 

Not applicable on this 

model.

“Y2” Potentiometer setting:

 

Not applicable on this 

model.

2-10V Operation

A CO

2

 sensor or other device sending a 2-10V signal 

can be used to control the damper motor. Two control 
methods are available to control the damper motor:
•  Method 1: The control board will accept a 

2-10VDC signal with a resistive load greater than 
5000 ohms. Bard CO

2

 sensor part #8403-096 can 

be used when the 2-10V output is connected to 
the "CO2 V IN" tab on the CRV control board. The 
pre-purge "PP" and occupied "OCC" potentiometer 
settings must be set to the off position and pre-
purge jumper must be set to "0" position for total 
modulation. The OCC potentiometer can be used 
to maintain a minimum blade position when "3" is 
energized.

•  Method 2: The damper motor will accept a 

2-10VDC signal with a resistive load less than 
5000 ohms. This method involves bypassing the 
control board and powering the motor directly from 
the device providing the 2-10VDC modulating 
signal. The 1/4" tab connector of the white wire 
coming from the damper motor lead must be 
disconnected from the CRV control board wiring. 
The 2-10V signal coming from the CO

2

 controller 

must be connected to this wire.

During 2-10VDC operation with "3" energized and 
pre-purge timed operation active, DC voltage signaling 
occupancy from a source such as a CO

2

 sensor will 

increase ventilation amounts as needed.

Adding Optional Co

2

 Control Sensor

Adding an optional CO

2

 control sensor (Bard Part 

#8403-096) to this control will maximize the 
capabilities of this vent by only supplying fresh air intake 
to maintain CO

2

 levels. This has multiple benefits.

•  Minimizes ventilation load on structure as it only 

brings in what is required to maintain CO

2

 levels 

thus lowering reconditioning requirements (not 
having to heat/cool as much outside air).

•  Will self-adjust for various occupancy levels so 

that fresh air is not being brought in beyond need. 
For example, if a room is designed for a maximum 
occupancy of 40 persons (standard ventilation 
control would have to be set for that occupancy), 
but the room typically only contains 25 persons. 
This control will self-adjust the amount of fresh air 
intake from 600 to 375 CFM automatically (based 
upon 15 CFM per person standard rate to ASHRAE 
standards).

Basic Installation

1.  Make sure power is turned off to the unit
2.  Run four (4) wire thermostat wire from the unit to 

the desired CO

2

 sensor location.

3.  Follow Figure 5 on page 8 to configure the CO

2

 

sensor for proper operation. 

4.  Connect the thermostat wiring from the CO

2

 sensor 

to step control assembly following the wiring diagram 
in Figure 4 or the one on the ventilator assembly.

5.  To check operation, restore power to the unit.
6.  Make sure that thermostatic control is in 

“occupied” mode of operation calling for 
ventilation. Terminal “3” on the low voltage 
terminal strip must be energized to open damper.

7.  Have someone stand in front of the CO

2

 sensor 

and breathe on it. The display should show an 
increase in CO

2

 ppm, and the damper blade in the 

ventilation package should increase. (It may be 
best to have two people to do this—one to breathe 
on control and one to observe damper.)

Summary of Contents for QCRV-4

Page 1: ...cturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 764 Supersedes NEW Date 1 19 22 Commercial Room Ventilator with Exhaust and Optional CO2 Modulation Model QCRV 4 920 0540 For Use with...

Page 2: ...ard Sequence of Operation 5 Adding Optional CO2 Control Sensor 6 Figures Figure 1 Adjusting OCC Potentiometer on CRV Control Board 3 Figure 2 CRV Installation and Adjustment 4 Figure 3 CRV Control Boa...

Page 3: ...with built in exhaust provisions FIGURE 1 Adjusting OCC Potentiometer on CRV Control Board QCRV 4 The QCRV 4 has a spring return damper blade If vent operation is no longer required or in the event of...

Page 4: ...pressure drop 3 Indoor blower motor speed 4 Damper blade open position setting for each mode of operation 5 Tightness or looseness of building envelope To determine the amount of fresh air that will b...

Page 5: ...rminal strip is energized indicating occupancy Once the selected time has passed the blade will move to the position set by the OCC potentiometer OCC Potentiometer setting This potentiometer can be us...

Page 6: ...nsor Bard Part 8403 096 to this control will maximize the capabilities of this vent by only supplying fresh air intake to maintain CO2 levels This has multiple benefits Minimizes ventilation load on s...

Page 7: ...tuator Motor BROWN WHITE 2 BLACK P3 3 P3 2 P3 1 OPTIONAL CO2 CONTROL REQUIRED FIELD WIRING FOR 1 B ON OFF CO2 CONTROL Unused Tape off 3 TERMINAL STRIP A B CRV CONTROL BOARD UNIT LOW VOLT B SETTING KEY...

Page 8: ...O CHANGE ANY SETTINGS WITH THE SIDE BUTTONS TO LOCK THE CO2 DIP SWITCHES MUST BE POSITIONED AS SHOWN FOR PROPER OPERATION MIS 4025 C Settings Recommended Default RON RELAY ON SET POINT 725 ROF RELAY O...

Reviews: