5 of 8

4.  Energize ventilator and adjust OCC potentiometer 

to open the blade to the desired position on the 
QCRV-4 (see Figure 1 on page 3). Label on right 
side of QCRV indicates the A, B, C, D and E 
positions. Remove filter for better viewing.

5.  Program thermostat, CS2000A or DDC control 

system to turn on ventilator during occupied 
periods only.

CRV Board Sequence of Operation

The “V” Ventilation option includes a control board with 
blade positioning potentiometers along with an input 
for a 2-10V input signal (see Figure 3).
Adjustable potentiometers:

“PP” Potentiometer setting:

 This potentiometer can be 

used to adjust the blade setting for outdoor air intake 
during a pre-purge cycle. The pre-purge cycle time is 
based on the setting of the pre-purge timer. The pre-
purge time can be set to 0, 30, 60 or 90 minutes using 
the PP jumper on the CRV control board. The pre-purge 
function is triggered when the "3" terminal on the low 
voltage terminal strip is energized, indicating occupancy. 
Once the selected time has passed, the blade will move 
to the position set by the "OCC" potentiometer.

“OCC” Potentiometer setting:

 This potentiometer can 

be used to adjust the blade setting for outdoor air 
intake when the "3" terminal is energized on the low 
voltage terminal strip indicating occupancy. The control 
board will energize the occupied setting after the pre-
purge cycle or immediately if pre-purge jumper is set to 
the "0" position.

MIS-4362 A

WHEN Y2 IS ENERGIZED

Y1 WILL OVERRIDE OCC

30

SETTING FOR 2ND STAGE

60

90

TURN OFF FOR C02

COOLING OR BLADE POSITION

FULL MODULATION

PRE-PURGE

TIMER

POT "Y1" SETTING FOR

STAGE ONE COOLING

POT "OCC" OCCUPIED SETTING

POT "PP" PRE-PURGE

SET FOR PREOCCUPANCY

0

POT "Y1" SETTING -- 

NOT APPLICABLE ON 

THIS MODEL

POT "Y2" SETTING -- 

NOT APPLICABLE ON 

THIS MODEL

POT "OCC" OCCUPIED SETTING 

-- TURN OFF FOR CO2 FULL 

MODULATION

PRE-PURGE TIMER

POT "PP" PRE-PURGE -- 

SET FOR PREOCCUPANCY

TABLE 1

QCRV-4 Ventilation Mode

Damper

Position

Duct-Free

Static Pressure

0.1

0.3

0.5

A

140

135

125

120

B

180

170

160

160

C

220

210

205

195

D

315

315

315

290

E

410

400

385

380

FIGURE 3

CRV Control Board

Summary of Contents for QCRV-4

Page 1: ...cturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 764 Supersedes NEW Date 1 19 22 Commercial Room Ventilator with Exhaust and Optional CO2 Modulation Model QCRV 4 920 0540 For Use with...

Page 2: ...ard Sequence of Operation 5 Adding Optional CO2 Control Sensor 6 Figures Figure 1 Adjusting OCC Potentiometer on CRV Control Board 3 Figure 2 CRV Installation and Adjustment 4 Figure 3 CRV Control Boa...

Page 3: ...with built in exhaust provisions FIGURE 1 Adjusting OCC Potentiometer on CRV Control Board QCRV 4 The QCRV 4 has a spring return damper blade If vent operation is no longer required or in the event of...

Page 4: ...pressure drop 3 Indoor blower motor speed 4 Damper blade open position setting for each mode of operation 5 Tightness or looseness of building envelope To determine the amount of fresh air that will b...

Page 5: ...rminal strip is energized indicating occupancy Once the selected time has passed the blade will move to the position set by the OCC potentiometer OCC Potentiometer setting This potentiometer can be us...

Page 6: ...nsor Bard Part 8403 096 to this control will maximize the capabilities of this vent by only supplying fresh air intake to maintain CO2 levels This has multiple benefits Minimizes ventilation load on s...

Page 7: ...tuator Motor BROWN WHITE 2 BLACK P3 3 P3 2 P3 1 OPTIONAL CO2 CONTROL REQUIRED FIELD WIRING FOR 1 B ON OFF CO2 CONTROL Unused Tape off 3 TERMINAL STRIP A B CRV CONTROL BOARD UNIT LOW VOLT B SETTING KEY...

Page 8: ...O CHANGE ANY SETTINGS WITH THE SIDE BUTTONS TO LOCK THE CO2 DIP SWITCHES MUST BE POSITIONED AS SHOWN FOR PROPER OPERATION MIS 4025 C Settings Recommended Default RON RELAY ON SET POINT 725 ROF RELAY O...

Reviews: