Low Voltage Connections
These units use a grounded 24 volt AC low voltage
circuit.
The
“R”
terminal is the
hot
terminal and the
“C”
terminal is
grounded.
“G”
terminal or pins 6 and 1 of P2 are the
fan inputs
.
Both must be energized for proper fan operation.
This is done automatically in the factory-installed
climate control options. If the climate control option is
abandoned and connections are made directly to P2,
both pins 6 and 1 of P2 must be energized for proper
operation.
“Y1”
terminal or pin 7 of P2 is the
first stage cooling
input
.
“W1”
terminal or pin 8 of P2 is the
first stage heating
input.
“R”
terminal or pin 10 of P2 is
24 VAC hot
.
“C”
terminal or pin 11 of P2 is
24 VAC grounded.
“Y2”
terminal or pin 12 of P2 is the
second stage
cooling input.
“W2”
terminal or pin 9 of P2 is
second stage heating
output
.
“3”
terminal of pin 5 of P2 is the
ventilation input
.
This terminal energizes any factory installed ventilation
option.
Fan Only
Energize G
1st Cooling Mode
Energize Y1, G
2nd Cooling Mode
Energize Y1, Y2, G
1st Stage Heating
Energize G, W1
2nd Stage Heating
Energize G, W1, W2
Ventilation
Energize G, 3
Low Voltage Connections for
DDC Control
FIGURE 17
Blower Motor Low Voltage Wire Harness Plug
MIS-1285
Summary of Contents for QC Series
Page 6: ...Manual 2100 416L Page 6 of 29 FIGURE 1 Unit Dimensions...
Page 16: ...Manual 2100 416L Page 16 of 29 FIGURE 12 Fresh Air Damper Removal MOUNTING SCREW...
Page 23: ...Manual 2100 416L Page 23 of 29 FIGURE 18 Remote Thermostat Wiring Diagram X Option...
Page 24: ...Manual 2100 416L Page 24 of 29 FIGURE 19 Remote Thermostat Wiring Diagram D Thermostat Option...