Manual 2100-742B
Page
52 of 57
1
Values listed are with ventilation package disabled
2
Return air temperature °F @ Default airflow (900 CFM) for AC tests and Balanced Climate airflow (650 CFM) for
dehumidification tests
3
Suction pr/- 4 psi, Discharge pr/- 10 psi
DB/WB
2
OD Temp.
75°F
85°F
95°F
Mode
A/C
Dehum
A/C
Dehum
A/C
Dehum
75/64.1
(55% RH)
Total Cooling Btuh
29,700
11,900
28,100
7,900
26,600
4,100
Sensible Btuh
20,400
3,300
19,700
200
19,300
(2,800)
S/T
0.687
0.28
0.701
0.03
0.726
0
Latent Btuh
9,300
8,600
8,400
7,700
7,300
6,900
Lbs. H20/hr.
8.8
8.1
7.9
7.3
6.9
6.5
Supply Air DB
53.5
70.7
54.3
74.8
55.3
78.8
Supply Air WB
52.4
58.5
53.1
60.5
54.0
62.4
Suction PSIG
3
125
123
127
127
130
130
Discharge PSIG
3
314
274
358
304
406
336
75/65.5
(60% RH)
Total Cooling Btuh
30,700
12,800
28,900
8,900
27,400
5,100
Sensible Btuh
19,300
2,600
18,500
(500)
18,000
(3,500)
S/T
0.629
0.203
0.640
0
0.657
0
Latent Btuh
11,400
10,200
10,400
9,400
9,400
8,600
Lbs. H20/hr.
10.8
9.6
9.8
8.9
8.9
8.1
Supply Air DB
54.8
71.6
55.5
75.7
56.5
79.7
Supply Air WB
53.7
59.6
54.5
61.5
55.4
63.4
Suction PSIG
3
128
126
131
130
133
133
Discharge PSIG
3
316
277
360
307
408
339
75/66.7
(65% RH)
Total Cooling Btuh
31,500
13,800
29,700
10,000
28,200
6,200
Sensible Btuh
18,000
1,900
17,200
(1,300)
16,700
(4,300)
S/T
0.571
0.14
0.579
0
0.592
0
Latent Btuh
13,500
11,900
12,500
11,300
11,500
10,500
Lbs. H20/hr.
12.7
11.2
11.8
10.7
10.8
9.9
Supply Air DB
56.1
72.5
56.8
76.7
57.8
80.7
Supply Air WB
55.1
60.6
55.9
62.6
56.8
64.5
Suction PSIG
3
131
129
134
133
137
136
Discharge PSIG
3
318
279
362
310
410
341
Q30H4D Cooling and Dehumidification Application Data
1