TABLE 12
Electrical Specifications − Q**H4 Series
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
The “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest
version), Article 310 for power conductor sizing.
CAUTION:
When more than one (1) field power circuit is run through one conduit, the conductors must be derated. Pay special attention
to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) conductors are in a raceway.
Maximum KW that can operate with the heat pump on is 9KW. Full heat available during emergency heat mode.
Model
Rated
Volts &
Phase
No. Field
Power
Circuits
Single Circuit
Dual Circuit
Minimum
Circuit
Ampacity
Maximum
External
Fuse or
Ckt. Brkr.
Field
Power
Wire
Size
Ground
Wire
Minimum
Circuit
Ampacity
Maximum
External
Fuse or
Ckt. Breaker
Field Power
Wire Size
Ground
Wire Size
Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B
Q24H4-A0Z
-A05
230/208-1
1
1
24
50
35
50
8
8
10
10
Q24H4-B0Z
-B06
-B09
230/208-3
1
1
1
16
34
43
20
35
45
12
8
8
12
10
10
Q24H4-C0Z
-C06
-C09
460-3
1
1
1
12
21
25
15
25
25
14
12
10
14
12
10
Q30H4-A0Z
-A05
230/208-1
1
1
25
51
35
60
8
6
10
10
Q30H4-B0Z
-B06
-B09
230/208-3
1
1
1
19
37
46
25
40
50
10
8
8
10
10
10
Q30H4-C0Z
-C06
-C09
460-3
1
1
1
10
19
23
15
20
25
14
12
10
14
12
10
Q36H4-A0Z
-A05
-A10
230/208-1
1
1
1 or 2
27
53
79
40
60
80
8
6
4
10
10
8
52
27
60
30
6
10
10
10
Q36H4-B0Z
-B06
-B09
-B15
230/208-3
1
1
1
1
21
39
48
48
30
45
50
50
10
8
8
8
10
10
10
10
Q36H4-C0Z
-C06
-C09
-C15
460-3
1
1
1
1
12
21
25
34
15
25
25
35
14
10
10
8
14
10
10
10
Q43H4-A0Z
-A05
-A10
230/208-1
1
1
1 or 2
33
59
85
40
60
90
8
6
4
10
10
8
59
26
60
30
6
10
10
10
Q43H4-B0Z
-B06
-B09
-B15
230/208-3
1
1
1
1
26
44
53
53
30
50
60
60
10
8
6
6
10
10
10
10
Q43H4-C0Z
-C06
-C09
-C15
460-3
1
1
1
1
11
20
25
25
15
20
25
30
14
12
10
10
14
12
10
10
Q48H4-A0Z
-A05
-A10
-A15
230/208-1
1
1
1 or 2
1 or 2
34
60
86
86
40
60
90
90
8
6
3
3
10
10
8
8
59
59
26
26
60
60
30
30
6
6
10
10
10
10
10
10
Q48H4-B0Z
-B06
-B09
-B15
230/208-3
1
1
1
1
27
45
54
54
30
50
60
60
10
8
6
6
10
10
10
10
Q48H4-C0Z
-C06
-C09
-C15
460-3
1
1
1
1
12
21
25
26
15
25
25
30
14
10
10
10
14
10
10
10
IMPORTANT:
While this electrical data is presented as a guide, it is important to electrically connect properly
sized fuses and conductor wires in accordance with the National Electrical Code and all local
codes.