Manual 7960-923
Page
7 of 10
1
Values listed are with ventilation package disabled
2
Return air temperature °F @ Default airflow (1300 CFM) for AC tests and Balanced Climate airflow (910 CFM) for
dehumidification tests
3
Suction pr/- 4 psi, Discharge pr/- 10 psi
DB/WB
2
OD Temp.
75°F
85°F
95°F
Mode
A/C
Dehum
A/C
Dehum
A/C
Dehum
075/64.1
(55% RH)
Total Cooling Btuh
38,300
16,000
36,300
11,600
34,300
7,100
Sensible Btuh
26,700
4,600
25,800
1,300
24,800
(2,000)
S/T
0.697
.029
0.711
0.11
0.723
0
Latent Btuh
11,600
11,400
10,500
10,300
9,500
9,100
Lbs. H20/hr.
10.9
10.8
9.9
9.7
9.0
8.6
Supply Air DB
54.3
70.2
55.0
73.9
55.7
77.6
Supply Air WB
52.8
57.7
53.5
59.6
54.1
61.4
Suction PSIG
3
129
121
131
124
134
127
Discharge PSIG
3
320
280
363
311
409
343
75/65.5
(60% RH)
Total Cooling Btuh
38,700
17,100
37,100
12,600
35,100
8,200
Sensible Btuh
25,100
3,700
24,200
400
23,200
(2,900)
S/T
0.649
0.216
0.652
0.032
0.661
0
Latent Btuh
13,600
13,400
12,900
12,200
11,900
11,100
Lbs. H20/hr.
12.8
12.6
12.2
11.5
11.2
10.5
Supply Air DB
55.6
71.2
56.3
75.0
57.1
78.7
Supply Air WB
54.3
58.9
54.9
60.7
55.6
62.6
Suction PSIG
3
132
124
134
127
137
130
Discharge PSIG
3
317
283
367
314
414
346
75/66.7
(65% RH)
Total Cooling Btuh
39,500
18,100
37,900
13,700
35,800
9,200
Sensible Btuh
23,500
2,800
22,500
(500)
21,600
(3,800)
S/T
0.595
0.15
0.594
0
0.603
0
Latent Btuh
16,000
15,300
15,400
14,200
14,200
13,000
Lbs. H20/hr.
15.1
14.4
14.5
13.4
13.4
12.3
Supply Air DB
57.0
72.3
57.7
76.1
58.4
79.8
Supply Air WB
55.8
60.0
56.4
61.9
57.1
63.7
Suction PSIG
3
135
127
138
130
140
134
Discharge PSIG
3
321
287
372
317
419
350
Q42A4D Cooling and Dehumidification Application Data