Manual 2100-752C
Page
39 of 41
Model
Rated ESP*
Maximum ESP*
Vent*
Rated CFM*
Balanced Climate
CFM*
Q36A4D
0.15
0.5
1100
1150
800
Q42A4D
0.15
0.5
1300
1300
910
Q48A4D
0.20
0.5
1500
1500
1050
* These units are equipped with a variable speed (ECM) indoor motor that automatically adjusts itself to maintain
approximately the same rate of indoor airflow in both heating and cooling, dry and wet coil conditions and at
both 230/208 or 460 volts.
These electric heaters are available in 230/208V units only.
These electric heaters are available in 480V units only.
TABLE 10
Indoor Blower Performance
TABLE 11
Maximum ESP of Operation
Electric Heat Only
Values shown are for units equipped
with standard 1" throwaway filter or 1"
washable filter.
Derate ESP by .15 for 2" pleated filters.
Nominal
KW
At 240V
At 208V
At 480V
At 460V
KW
1-Ph
Amps
3-Ph
Amps BTUH
KW
1-Ph
Amps
3-Ph
Amps BTUH
KW
3-Ph
Amps BTUH
KW
3-Ph
Amps BTUH
5.0
5.0
20.8
17,065 3.75 18.0
12,799
6.0
6.0
14.4 20,478 4.50
12.5 15,359
6.0
7.2
20,478 5.52
6.9
18,840
9.0
9.0
21.7 30,717 6.75
18.7 23,038
9.0
10.8 30,717 8.28 10.4 28,260
10.0
10.0 41.7
34,130 7.50 36.1
25,598
15.0
15.0 62.5
36.1 51,195 11.25 54.1
31.2 38,396 15.0 18.0 51,195 13.80 17.3 47,099
TABLE 12
Electric Heat
Model
All
Outlet
Top
Speed
Rated
-A0Z
-A05
-A10
-A15
.50
.50
.50
.50
-B0Z
-B06
-B09
-B15
.50
.50
.50
.50
-C0Z
-C06
-C09
-C15
.50
.50
.50
.50