background image

Manual 2100-354
Page

23

FAN BLADE SETTINGS

Shown in Figure 13 are the correct fan blade setting
dimensions for proper air delivery across the outdoor coil.

Any service work requiring removal or adjustment in the
fan and/or motor area will require that the dimensions in
Table 14 be checked and blade adjusted in or out on the
motor shaft accordingly.

SERVICE

SERVICE HINTS

1. Caution homeowner to maintain clean air filters at all

times.  Also, not to needlessly close off supply and
return air registers.  This reduces air flow through the
system which shortens equipment service life as well
as increasing operating costs.

2. Switching to heating cycle at 75°F or higher outside

temperature may cause a nuisance trip of the manual
reset high pressure switch.

3. The heat pump wall thermostats perform multiple

functions.  Be sure that all function switches are
correctly set for the desired operating mode before
trying to diagnose any reported service problems.

4. Check all power fuses or circuit breakers to be sure

that they are the correct rating.

5. Periodic cleaning of the outdoor coil to permit full and

unrestricted airflow circulation is essential.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed.  Pressure tables can be found in Tables 16
through 23 in this manual covering all models on both
cooling and heating cycles.  It is imperative to match the
correct pressure table to the unit by model number.

REFRIGERANT CHARGE

The correct system R-22 charge is shown on the unit rating
plate.  Optimum unit performance will occur with a
refrigerant charge resulting in a suction line temperature
(6” from compressor) as shown in Table 13.

FIGURE  13

FAN BLADE SETTING

MIS-1190

TABLE  14

FAN BLADE SETTING

DIMENSIONS

l

e

d

o

M

n

o

i

s

n

e

m

i

D

"

A

"

4

2

1

1

H

P

4

2

2

1

H

P

"

0

0

.

1

0

3

1

1

H

P

0

3

2

1

H

P

6

3

1

1

H

P

6

3

2

1

H

P

"

5

7

.

2

2

4

1

1

H

P

2

4

2

1

H

P

8

4

0

1

H

P

8

4

2

1

H

P

0

6

0

1

H

P

"

5

7

.

1

The above suction line temperatures are based upon
80°F dry bulb/67°F wet bulb (50% RH) temperature and
rated airflow across the evaporator during cooling cycle.

TABLE  13

l

e

d

o

M

d

e

t

a

R

w

o

l

f

r

i

A

D

O

°

5

9

e

r

u

t

a

r

e

p

m

e

T

D

O

°

2

8

e

r

u

t

a

r

e

p

m

e

T

2

4

2

1

1

H

P

0

0

8

7

5

-

6

5

7

6

-

5

6

1

4

2

2

1

H

P

0

0

8

6

6

-

4

6

9

6

-

7

6

0

3

1

1

H

P

0

0

0

1

8

5

-

6

5

0

6

-

8

5

0

3

2

1

H

P

0

0

0

1

8

5

-

6

5

0

6

-

8

5

6

3

1

1

H

P

0

0

1

1

2

5

-

0

5

4

5

-

2

5

6

3

2

1

H

P

0

0

1

1

2

5

-

0

5

4

5

-

2

5

2

4

1

1

H

P

0

0

4

1

6

5

-

4

5

9

5

-

7

5

2

4

2

1

H

P

0

0

4

1

6

5

-

4

5

9

5

-

7

5

8

4

0

1

H

P

0

5

5

1

7

5

-

5

5

0

6

-

8

5

8

4

2

1

H

P

0

5

5

1

7

5

-

5

5

9

5

-

7

5

0

6

0

1

H

P

0

0

7

1

4

5

-

2

5

9

5

-

7

5

Summary of Contents for PH11242

Page 1: ...H1230 PH11361 PH1236 PH11422 PH1242 PH10481 PH11481 PH1060 INSTALLATION INSTRUCTIONS Copyright 2003 Manual 2100 354B Supersedes 2100 354A File Volume II Tab 11 Date 03 19 03 Bard Manufacturing Company...

Page 2: ...e 4 Roof Top Application 11 Figure 5 Elevated Mounting Platforms 11 Figure 6 Prefabricated Rood Curb Specifications 12 Figure 7 Field Fabricated Curbing 13 Figure 8 Condensate Drain Trap 14 Figure 9 L...

Page 3: ...and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Co...

Page 4: ...cularly Starting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide they do not supersede any national and or local cod...

Page 5: ...s s e r p m o C e p y T r o s s e r p m o C l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S s t l o V 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 0 6 4 8 0 2 0 3 2 s p m A...

Page 6: ...m o C e p y T r o s s e r p m o C l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S s t l o V 8 0 2 0 3 2 8 0 2 0 3 2 0 6 4 8 0 2 0 3 2 8 0 2 0 3 2 0 6 4 s p m A d a o L d e t a...

Page 7: ...S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S s t l o V 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 s p m A d a o L d e t a R 5 0 1...

Page 8: ...N A N S A N S A A A N A N 5 0 A C P 3 H E 1 8 0 2 0 4 2 A N S A N S A N A N A N S A N 0 1 A C P 3 H E 1 8 0 2 0 4 2 A N S A N A N A N A N A N A N A N 5 1 A C P 3 H E 1 8 0 2 0 4 2 A N A N A N S 2 A N...

Page 9: ...0 5 7 5 2 1 1 5 7 3 0 5 7 5 2 1 1 0 0 8 2 1 0 0 5 0 2 0 0 0 6 2 0 0 4 8 3 0 0 8 2 1 0 0 0 6 2 0 0 4 8 3 1 8 1 8 0 2 8 8 2 3 3 3 2 6 3 6 1 4 1 4 5 5 2 6 1 8 1 8 0 2 2 6 3 6 1 4 1 4 5 5 2 6 0 6 0 3 0 6...

Page 10: ...m o N s e h c n I g n i n e p O t c u D H e g r a h c s i D r i A n r u t e R A B C J K L M D E F G 4 2 1 1 H P 4 2 2 1 H P 0 3 1 1 H P 0 3 2 1 H P 6 3 1 1 H P 6 3 2 1 H P 4 1 4 2 6 1 3 8 4 8 1 8 3 8...

Page 11: ...of twelve inch elevation is recommended while greater elevation may be required for areas of high snow accumulation Poured concrete steel framework brick cement block etc can be utilized to construct...

Page 12: ...Manual 2100 354 Page 10 FIGURE 2 SLAB MOUNTING AT GROUND LEVEL Above 32 F Outside Temperature FIGURE 3 AIRFLOW AND SERVICE ACCESS CLEARANCES MIS 1185...

Page 13: ...Manual 2100 354 Page 11 FIGURE 4 ROOF TOP APPLICATION May also be required for ground level installations MIS 1176 FIGURE 5 ELEVATED MOUNTING PLATFORMS MIS 1183...

Page 14: ...e d o M s l i a t e D b r u C f o o R A B C D E F G H I J K L 4 2 1 1 H P 4 2 2 1 H P 0 3 1 1 H P 0 3 2 1 H P 6 3 1 1 H P 6 3 2 1 H P 6 3 E H R 3 0 0 2 4 0 9 5 7 3 0 8 5 2 0 4 5 2 7 3 5 7 3 8 3 5 7 3...

Page 15: ...wood curbing Caulk seal all joints weatherproof TABLE 7 DIMENSION X FOR FIELD FABRICATEDCURBING l e d o M t i n U d o o H f o o R l e d o M n o i s n e m i D X 4 2 1 1 H P 4 2 2 1 H P 0 3 1 1 H P 0 3...

Page 16: ...be piped through a condensate drain trap to a suitable drain C Always mount the unit is such a position that it may be easily reached for servicing and maintenance D Insure that the unit is clear so...

Page 17: ...els are suitable for connection with copper wire only These instructions must be adhered to Refer to the National Electrical Code for complete current carrying capacity data on the various insulation...

Page 18: ...h c t i w S n a F t a e H x u A t a e H m E k c e h C s p m a L g n i t a c i d n I 7 1 0 3 0 4 8 9 2 1 1 R 4 7 8 T 9 0 0 4 0 4 8 1 8 1 1 L 4 7 6 Q r e v o e g n a h c l a u n a M b l u b y r u c r e...

Page 19: ...ion point in the unit and while the unit is operating at full load maximum amperage operating condition COMPRESSOR CUTOFF THERMOSTAT and OUTDOOR THERMOSTAT WIRING Heat pump compressor operation at out...

Page 20: ...0 6 4 0 3 2 3 1 8 4 2 1 H P 5 1 0 3 2 1 B 1 8 4 2 1 H P 5 1 0 3 2 1 0 6 0 1 H P 0 2 5 1 0 3 2 1 C B 0 6 0 1 H P 8 1 5 1 0 6 4 0 3 2 3 TABLE 11 5 thru 10 KW l e d o M W K s t l o V e s a h P 2 4 2 1 1...

Page 21: ...sors are wired identically internally As a result once the correct phasing is determined for a specific system or installation connecting properly phased power leads to the same Fusite terminals shoul...

Page 22: ...nected to terminal 60 and reconnect to desired terminal Refer to Figure 12 The manufacturer s recommendation is for 60 minute defrost cycles There is a cycle speed up jumper on the control This can be...

Page 23: ...o h s r o n e p o r o f k c e h C g n i d n i w r o t c a t n o c e c a l p e R r o t o m r o o d t u o n a F n u r t o n s e o d g n i t a e h r o g n i l o o c t s o r f e d g n i r u d t p e c x e...

Page 24: ...0 8 4 0 9 4 0 0 5 5 8 9 6 5 4 8 2 5 5 0 4 6 3 5 1 5 0 2 5 4 1 5 0 5 8 2 0 9 4 0 9 5 7 4 0 0 2 6 4 5 5 8 4 4 4 5 5 3 4 5 9 2 2 4 7 7 0 1 4 8 9 8 9 3 7 5 7 8 3 2 5 6 7 3 3 8 5 6 3 8 4 5 5 3 5 4 5 4 3 4...

Page 25: ...led on all units so that the system operating pressures can be observed Pressure tables can be found in Tables 16 through 23 in this manual covering all models on both cooling and heating cycles It is...

Page 26: ...und the circumference to flow braze material completely around the joint Slowly move torch into Area 3 to draw braze material into joint See Figure 14 Do not overheat joint MIS 1179 FIGURE 14 BRAZINGD...

Page 27: ...k c e h C d e e p s M F C h g i h t a s f f u p r o s t n u H g n i f f u p e c u d e r r e t l i f r o l e n a p g n i v o m e r s e o D n o i t c i t s e r e c u d e R w o l f r i a m u m i x a m e...

Page 28: ...w s c a i r T r o f k c e h C y a l e r N O T P M Y S E R U D E C O R P E S U A C e s i o n e v i s s e c x E e s i o n r o t o m r o t c u d t e n i b a c e s i o n r i a s i t i f i e n i m r e t e...

Page 29: ...7 2 3 2 1 8 2 5 2 3 8 1 7 2 5 8 0 9 2 7 8 9 0 3 9 8 8 2 3 1 9 8 4 3 3 9 7 6 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 3 8 0 2 2 5 8 0 4 2 7 8 0 6 2 9 8 0 8 2 1 9 0 0 3 3 9 0 2 3 5 9...

Page 30: ...7 2 3 2 0 8 9 4 2 1 8 5 6 2 3 8 3 8 2 4 8 0 0 3 5 8 8 1 3 6 8 7 3 3 7 8 6 5 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 1 8 4 2 2 3 8 0 4 2 6 8 8 5 2 7 8 4 7 2 9 8 2 9 2 0 9 1 1 3 1 9...

Page 31: ...g i H 8 7 3 1 2 0 8 8 2 2 1 8 3 4 2 3 8 0 6 2 4 8 7 7 2 5 8 5 9 2 7 8 5 1 3 8 8 4 3 3 0 9 5 5 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 1 8 0 2 2 3 8 6 3 2 4 8 2 5 2 6 8 9 6 2 7 8 7...

Page 32: ...h g i H 2 8 8 0 2 4 8 4 2 2 5 8 9 3 2 6 8 6 5 2 7 8 3 7 2 8 8 1 9 2 0 9 8 0 3 0 9 7 2 3 1 9 6 4 3 8 4 2 1 H P B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 2 7 3 0 2 4 7 1 5 2 6 7 0 3 2 7...

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ......

Page 37: ......

Page 38: ......

Page 39: ......

Reviews: