background image

Manual 2100-354
Page

9

INSTALLATION

LOCATION

GENERAL

The unit must be located outside, or in a well ventilated
area.  It must not be in the space being heated or cooled.  A
sound absorbing material should be considered if the unit
is to be installed in such a position or location that might
cause transmission of sound or vibration to the living area
or adjacent buildings.

SLAB MOUNTING

In areas where winter temperatures DO NOT go below
32° F for periods over twelve hours, the unit may be slab
mounted at grade level.  When installing unit at grade
level, install on a concrete slab at least four inches above
finished grade level.  Slab should have a slope tolerance
away from the building structure of at lease 1/4 inch per
foot, while being level from side to side.  This will prevent
ice buildup under the unit during defrost cycles.  Place slab
in a location where runoff water from higher ground will
not collect around unit.  See Figure 2.

A minimum of 18 inches should be provided between the
coil inlet and any building surfaces.  Provide at least four
feet between coil outlet and any building wall, fences or
other vertical structures.  Provide a minimum of three feet
clearance on the service access side of the unit.  See
Figure 3

ROOF MOUNTING

When a unit is installed in areas where low ambient
temperatures or strong winter winds exist, it should be
placed so prevailing winter winds are not in direct line
with the heat pump coil.  If this is not possible, a wind
barrier should be constructed.  Place barrier 24 inches
from the coil inlet side of the unit and in the direction of
prevailing winds.  Size barrier at least the same height and
width as the unit.  This may be necessary on ground level
installations, also.  See Figure 4.

WINTER INSTALLATION BELOW 32°F

In areas where winter conditions go below 32°F for
extended periods, the unit must be elevated above the
mounting surface to prevent snowfall or defrost ice
accumulation from interfering with the operation of the
unit.  A minimum of twelve inch elevation is
recommended, while greater elevation may be required for
areas of high snow accumulation.  Poured concrete, steel
framework, brick, cement block, etc., can be utilized to
construct a suitable raised mounting platform.  See
Figure 5.

TYPICAL INSTALLATIONS

1.

ROOF MOUNTED

  –  The unit is mounted on a

sturdy base on the roof of the building.  Return air to
the unit is brought through a single return grille (grilles
with built-in filters are best since they enable easy
access for filter changing).  Return air ducts are
attached to the lower section of the front panel.
Supply air is brought from the unit to attic duct work
or to a furred down hall.  Supply air duct is attached to
the top of the front panel.

CAUTION:  All outdoor duct work must be

thoroughly insulated and weatherproofed.  All
attic duct work must be thoroughly insulated.
Two inch thick insulation with suitable vapor
barrier is recommended for both outdoor and
attic runs.

In roof top installation, as in all installations, the heat
pump must be level from side to side.  However, the
unit should have a pitch along the length to assure
complete external drainage of precipitation and of
defrost condensate.  See Figures 6 and 7, and Tables  6
and 7.

2.

CRAWL SPACE

  –  Duct work installed in crawl

space must be well insulated and provided with a
vapor barrier.  In addition, the crawl space must be
thoroughly ventilated and provided with a good vapor
barrier as a ground cover.  It is most desirable to install
the unit outdoors rather than inside the crawl space, so
that it will be readily accessible for service.  In
addition, it is necessary to dispose of  the condensate
from the outdoor coil on the heating cycle, and this is
virtually impossible with the unit installed inside the
crawl space.

3.

SLAB MOUNTED AT GROUND LEVEL

    This

type installation is ideal for homes with a slab floor
construction where a roof mounted unit is not desired.
The supply and return duct work can be run through a
furred closet space.

4.

THROUGH THE WALL 

 –  This type installation

requires a suitable framework to be fabricated capable
of withstanding the unit weight.  Normally the unit will
be insulated so as to minimize supply and return duct
work.

Summary of Contents for PH11242

Page 1: ...H1230 PH11361 PH1236 PH11422 PH1242 PH10481 PH11481 PH1060 INSTALLATION INSTRUCTIONS Copyright 2003 Manual 2100 354B Supersedes 2100 354A File Volume II Tab 11 Date 03 19 03 Bard Manufacturing Company...

Page 2: ...e 4 Roof Top Application 11 Figure 5 Elevated Mounting Platforms 11 Figure 6 Prefabricated Rood Curb Specifications 12 Figure 7 Field Fabricated Curbing 13 Figure 8 Condensate Drain Trap 14 Figure 9 L...

Page 3: ...and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Co...

Page 4: ...cularly Starting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide they do not supersede any national and or local cod...

Page 5: ...s s e r p m o C e p y T r o s s e r p m o C l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S s t l o V 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 0 6 4 8 0 2 0 3 2 s p m A...

Page 6: ...m o C e p y T r o s s e r p m o C l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S s t l o V 8 0 2 0 3 2 8 0 2 0 3 2 0 6 4 8 0 2 0 3 2 8 0 2 0 3 2 0 6 4 s p m A d a o L d e t a...

Page 7: ...S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S s t l o V 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 s p m A d a o L d e t a R 5 0 1...

Page 8: ...N A N S A N S A A A N A N 5 0 A C P 3 H E 1 8 0 2 0 4 2 A N S A N S A N A N A N S A N 0 1 A C P 3 H E 1 8 0 2 0 4 2 A N S A N A N A N A N A N A N A N 5 1 A C P 3 H E 1 8 0 2 0 4 2 A N A N A N S 2 A N...

Page 9: ...0 5 7 5 2 1 1 5 7 3 0 5 7 5 2 1 1 0 0 8 2 1 0 0 5 0 2 0 0 0 6 2 0 0 4 8 3 0 0 8 2 1 0 0 0 6 2 0 0 4 8 3 1 8 1 8 0 2 8 8 2 3 3 3 2 6 3 6 1 4 1 4 5 5 2 6 1 8 1 8 0 2 2 6 3 6 1 4 1 4 5 5 2 6 0 6 0 3 0 6...

Page 10: ...m o N s e h c n I g n i n e p O t c u D H e g r a h c s i D r i A n r u t e R A B C J K L M D E F G 4 2 1 1 H P 4 2 2 1 H P 0 3 1 1 H P 0 3 2 1 H P 6 3 1 1 H P 6 3 2 1 H P 4 1 4 2 6 1 3 8 4 8 1 8 3 8...

Page 11: ...of twelve inch elevation is recommended while greater elevation may be required for areas of high snow accumulation Poured concrete steel framework brick cement block etc can be utilized to construct...

Page 12: ...Manual 2100 354 Page 10 FIGURE 2 SLAB MOUNTING AT GROUND LEVEL Above 32 F Outside Temperature FIGURE 3 AIRFLOW AND SERVICE ACCESS CLEARANCES MIS 1185...

Page 13: ...Manual 2100 354 Page 11 FIGURE 4 ROOF TOP APPLICATION May also be required for ground level installations MIS 1176 FIGURE 5 ELEVATED MOUNTING PLATFORMS MIS 1183...

Page 14: ...e d o M s l i a t e D b r u C f o o R A B C D E F G H I J K L 4 2 1 1 H P 4 2 2 1 H P 0 3 1 1 H P 0 3 2 1 H P 6 3 1 1 H P 6 3 2 1 H P 6 3 E H R 3 0 0 2 4 0 9 5 7 3 0 8 5 2 0 4 5 2 7 3 5 7 3 8 3 5 7 3...

Page 15: ...wood curbing Caulk seal all joints weatherproof TABLE 7 DIMENSION X FOR FIELD FABRICATEDCURBING l e d o M t i n U d o o H f o o R l e d o M n o i s n e m i D X 4 2 1 1 H P 4 2 2 1 H P 0 3 1 1 H P 0 3...

Page 16: ...be piped through a condensate drain trap to a suitable drain C Always mount the unit is such a position that it may be easily reached for servicing and maintenance D Insure that the unit is clear so...

Page 17: ...els are suitable for connection with copper wire only These instructions must be adhered to Refer to the National Electrical Code for complete current carrying capacity data on the various insulation...

Page 18: ...h c t i w S n a F t a e H x u A t a e H m E k c e h C s p m a L g n i t a c i d n I 7 1 0 3 0 4 8 9 2 1 1 R 4 7 8 T 9 0 0 4 0 4 8 1 8 1 1 L 4 7 6 Q r e v o e g n a h c l a u n a M b l u b y r u c r e...

Page 19: ...ion point in the unit and while the unit is operating at full load maximum amperage operating condition COMPRESSOR CUTOFF THERMOSTAT and OUTDOOR THERMOSTAT WIRING Heat pump compressor operation at out...

Page 20: ...0 6 4 0 3 2 3 1 8 4 2 1 H P 5 1 0 3 2 1 B 1 8 4 2 1 H P 5 1 0 3 2 1 0 6 0 1 H P 0 2 5 1 0 3 2 1 C B 0 6 0 1 H P 8 1 5 1 0 6 4 0 3 2 3 TABLE 11 5 thru 10 KW l e d o M W K s t l o V e s a h P 2 4 2 1 1...

Page 21: ...sors are wired identically internally As a result once the correct phasing is determined for a specific system or installation connecting properly phased power leads to the same Fusite terminals shoul...

Page 22: ...nected to terminal 60 and reconnect to desired terminal Refer to Figure 12 The manufacturer s recommendation is for 60 minute defrost cycles There is a cycle speed up jumper on the control This can be...

Page 23: ...o h s r o n e p o r o f k c e h C g n i d n i w r o t c a t n o c e c a l p e R r o t o m r o o d t u o n a F n u r t o n s e o d g n i t a e h r o g n i l o o c t s o r f e d g n i r u d t p e c x e...

Page 24: ...0 8 4 0 9 4 0 0 5 5 8 9 6 5 4 8 2 5 5 0 4 6 3 5 1 5 0 2 5 4 1 5 0 5 8 2 0 9 4 0 9 5 7 4 0 0 2 6 4 5 5 8 4 4 4 5 5 3 4 5 9 2 2 4 7 7 0 1 4 8 9 8 9 3 7 5 7 8 3 2 5 6 7 3 3 8 5 6 3 8 4 5 5 3 5 4 5 4 3 4...

Page 25: ...led on all units so that the system operating pressures can be observed Pressure tables can be found in Tables 16 through 23 in this manual covering all models on both cooling and heating cycles It is...

Page 26: ...und the circumference to flow braze material completely around the joint Slowly move torch into Area 3 to draw braze material into joint See Figure 14 Do not overheat joint MIS 1179 FIGURE 14 BRAZINGD...

Page 27: ...k c e h C d e e p s M F C h g i h t a s f f u p r o s t n u H g n i f f u p e c u d e r r e t l i f r o l e n a p g n i v o m e r s e o D n o i t c i t s e r e c u d e R w o l f r i a m u m i x a m e...

Page 28: ...w s c a i r T r o f k c e h C y a l e r N O T P M Y S E R U D E C O R P E S U A C e s i o n e v i s s e c x E e s i o n r o t o m r o t c u d t e n i b a c e s i o n r i a s i t i f i e n i m r e t e...

Page 29: ...7 2 3 2 1 8 2 5 2 3 8 1 7 2 5 8 0 9 2 7 8 9 0 3 9 8 8 2 3 1 9 8 4 3 3 9 7 6 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 3 8 0 2 2 5 8 0 4 2 7 8 0 6 2 9 8 0 8 2 1 9 0 0 3 3 9 0 2 3 5 9...

Page 30: ...7 2 3 2 0 8 9 4 2 1 8 5 6 2 3 8 3 8 2 4 8 0 0 3 5 8 8 1 3 6 8 7 3 3 7 8 6 5 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 1 8 4 2 2 3 8 0 4 2 6 8 8 5 2 7 8 4 7 2 9 8 2 9 2 0 9 1 1 3 1 9...

Page 31: ...g i H 8 7 3 1 2 0 8 8 2 2 1 8 3 4 2 3 8 0 6 2 4 8 7 7 2 5 8 5 9 2 7 8 5 1 3 8 8 4 3 3 0 9 5 5 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 1 8 0 2 2 3 8 6 3 2 4 8 2 5 2 6 8 9 6 2 7 8 7...

Page 32: ...h g i H 2 8 8 0 2 4 8 4 2 2 5 8 9 3 2 6 8 6 5 2 7 8 3 7 2 8 8 1 9 2 0 9 8 0 3 0 9 7 2 3 1 9 6 4 3 8 4 2 1 H P B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 2 7 3 0 2 4 7 1 5 2 6 7 0 3 2 7...

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ......

Page 37: ......

Page 38: ......

Page 39: ......

Reviews: