background image

Manual

2100-467D

Page

16 of 25

THREE PHASE SCROLL COMPRESSOR
START UP INFORMATION

(Model PA13361-B)

Scroll compressors, like several other types of
compressors, will only compress in one rotational
direction.  Direction of rotation is not an issue with
single phase compressors since they will always start
and run in the proper direction.

However, three phase compressors will rotate in either
direction depending upon phasing of the power.  Since
there is a 50-50 chance of connecting power in such a
way as to cause rotation in the reverse direction,
verification of proper rotation must be made.
Verification of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized.
Reverse rotation also results in an elevated sound level
over that with correct rotation, as well as, substantially
reduced current draw compared to tabulated values.

Verification of proper rotation must be made at the
time the equipment is put into service.

  If improper

rotation is corrected at this time there will be no
negative impact on the durability of the compressor.
However, reverse operation for over one hour may have
a negative impact on the bearing due to oil pump out.

NOTE: If compressor is allowed to run in reverse

rotation for several minutes the compressor’s
internal protector will trip.

All three phase scroll compressors are wired identically
internally.  As a result, once the correct phasing is
determined for a specific system or installation,
connecting properly phased power leads to the same
Fusite terminals should maintain proper rotation
direction.

The direction of rotation of the motor may be changed
by reversing any two line connections to the unit.

(Models PA13422-B, -C; PA13482-B, -C;
PA13602-B, -C)

All units with three phase scroll compressors are
equipped with a three phase line monitor to prevent
compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two
LED’s.  If the “Y” signal is present at the phase monitor
and phases are correct, the green LED will light.

If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.

If a fault condition occurs, reverse tow of the supply
leads to the unit.  Do not reverse any of the unit factory
wires as damage may occur.

SEQUENCE OF OPERATION

BLOWER ONLY

  –  When the “Fan” switch on the

room thermostat is placed in the “On” position (circuit
R-G makes), the blower will energize and run until the
“Fan” switch is placed back into the “Auto” position.
This will allow for constant air circulation at a lower
airflow during times when the unit is not in operation
for cooling or heating.

COOLING

  –  On a call for cooling from the room

thermostat (circuit R-Y makes), the blower will energize
(circuit R-G is automatic when R-Y makes) as well as
the compressor, and outdoor fan motor.  Note that if the
“Fan” switch on the room thermostat is in the “On”
position and the blower is already in operation, then the
motor will ramp up to the required speed for cooling.

HEATING (1st Stage)

  –  On a call for heating from

the room thermostat (circuit R-W1 makes), the blower
will energize (circuit R-G is automatic when R-W1
makes).  This will place the system into heating
operation to maintain the thermostat set temperature.
Note that if the “Fan” switch on the room thermostat is
in the “On” position and the blower is already in
operation, then the motor will ramp up to the required
speed for heating.

HEATING (2nd Stage)

  –  If the operation of the 1st

Stage electric heaters will not maintain the set room
temperature, then the thermostat will call for additional
heat to help maintain the set temperature.  On a call for
second stage heating from the room thermostat (circuit
R-W2 makes), additional electric heaters will be
energized if installed.

INDOOR BLOWER MOTOR

These models feature a variable speed (ECM) motor
providing high efficiency, low sound levels and soft
start capabilities.  The motor is self adjusting to provide
the proper airflow rate at duct static pressures up to
0.50" WC without user adjustment or wiring changes.

On command from the wall thermostat the motor will
start slowly and ramp up to full speed over a period of
10-15 seconds.

When the thermostat is satisfied the blower will operate
for approximately 1 minute, and then slow down and
stop.

COMPRESSOR CONTROL MODULE

The compressor control is an anti-short cycle/lockout
timer with high and low pressure switch monitoring and
alarm output.

START UP AND OPERATION

Summary of Contents for PA13241-A

Page 1: ...13361 B PA13422 A PA13422 B PA13422 C PA13482 A PA13482 B PA13482 C PA13602 A PA13602 B PA13602 C INSTALLATION INSTRUCTIONS Manual 2100 467D Supersedes 2100 467C File Volume II Tab 10 Date 08 12 08 Ba...

Page 2: ...tings 18 Pressure Tables 19 20 Suction and Discharge Tube Brazing 21 Troubleshooting ECM Blower Motors 22 25 Figures Figure 1 Unit Dimensions 8 Figure 2 Slab Mounting at Ground Level 10 Figure 3 Airfl...

Page 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Page 4: ...m should be carefully read before beginning the installation Note particularly Starting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a genera...

Page 5: ...o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S s t l o V 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 0 6 4 8 0 2 0...

Page 6: ...8 4 3 1 A P C 2 8 4 3 1 A P A 2 0 6 3 1 A P B 2 0 6 3 1 A P C 2 0 6 3 1 A P 5 0 A 3 1 3 P H E 1 8 0 2 0 4 2 X X X 0 1 A 3 1 3 P H E 1 8 0 2 0 4 2 X X X 5 1 A 3 1 3 P H E 1 8 0 2 0 4 2 X X 9 0 B 3 1 3...

Page 7: ...0 4 8 3 1 4 5 5 2 6 1 8 6 9 7 0 7 0 8 4 4 8 9 0 B 3 1 3 P H E 3 8 0 2 0 4 2 9 0 0 7 0 3 5 7 6 0 0 0 3 2 7 8 1 7 1 2 e n o N 1 4 2 8 2 5 2 0 3 0 1 0 1 0 1 5 1 B 3 1 3 P H E 3 8 0 2 0 4 2 5 1 0 0 2 1 5...

Page 8: ...package access panel Return opening Supply opening Drain access High voltage knockout Low voltage knockout Heater package knockout L W A E B C D F A C B C H height L length W width D E F G PA PH1324 1...

Page 9: ...All outdoor duct work must be thoroughly insulated and weatherproofed All attic duct work must be thoroughly insulated Two inch thick insulation with suitable vapor barrier is recommended for both out...

Page 10: ...re Condenser fan and motor access from top Leave 60 min above fan Side View Top View MIS 2143 between duct and any combustible material if distance between outside wall and unit is less than 3 feet ne...

Page 11: ...48 min 32 F or lower climate 12 min if in on surface of platform Both legs must rest 48 min 32 F or lower climate 12 min if in on surface of platform Both legs must rest Metal frame MIS 2144 Platform...

Page 12: ...w for expansion of water when it freezes AIR FILTERS Air filters for the return air side of the system are not provided as part of these models and must be field supplied and installed as part of the...

Page 13: ...l The electrical specifications list fuse and wire sizes 75 F copper for all models including the most commonly used heater sizes The unit rating plate lists a Maximum Time Delay Fuse or HACR type cir...

Page 14: ...Y Terminal R G C HEAT ON UNITS WITH 15 OR MORE KW C Low Voltage Wiring B R W RC R Y1 L G C G Block R E Y L Thermostat Subbase 3 1 2 W1 W2 F RC B Unit 24V REMOVE JUMPER FOR 2 STAGE ELECTRIC B YO 1120...

Page 15: ...recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leak...

Page 16: ...sor operation is inhibited If a fault condition occurs reverse tow of the supply leads to the unit Do not reverse any of the unit factory wires as damage may occur SEQUENCE OF OPERATION BLOWER ONLY Wh...

Page 17: ...never compressor is locked out due to HPC or LPC sequences as described NOTE Both high and low pressure switch controls are inherently automatic reset devices The high pressure switch and low pressure...

Page 18: ...he correct system R 410A charge is shown on the unit rating plate You can reference Tables 10 11 to validate proper system performance However it is recommended that if incorrect charge is suspected t...

Page 19: ...4 7 2 0 4 1 6 9 2 2 4 1 8 1 3 4 4 1 0 4 3 7 4 1 2 6 3 9 4 1 4 8 3 1 5 1 2 1 4 3 5 1 0 4 4 6 5 1 9 6 4 8 5 1 7 9 4 0 6 1 5 2 5 2 6 1 3 5 5 5 8 B D 2 7 B W e d i S w o L e d i S h g i H 5 4 1 1 6 2 8 4...

Page 20: ...4 7 3 1 5 6 4 9 3 1 2 9 4 0 4 1 0 2 5 2 4 1 7 4 5 0 8 B D 7 6 B W e d i S w o L e d i S h g i H 4 3 1 5 4 2 5 3 1 0 7 2 7 3 1 4 9 2 8 3 1 9 1 3 9 3 1 4 4 3 1 4 1 8 6 3 2 4 1 3 9 3 4 4 1 1 2 4 5 4 1 9...

Page 21: ...2 and 3 slowly and uniformly until braze material softens and the tube can be pulled out of suction fitting See Figure 9 To connect Recommended brazing materials silfos with minimum 5 silver or silver...

Page 22: ...sive noise Determine if it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause b...

Page 23: ...er to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted into...

Page 24: ...ry d Check the external static pressure total of both supply and return to insure that you are within the ranges as listed on the unit serial plate If higher than allowed additional duct work is neede...

Page 25: ...nd the appropriate motor terminal 1 5 G input is typically on terminal 1 but refer to wiring diagram a If the low voltage communication is not present check the demand from the thermostat Also check t...

Reviews: