background image

Manual 2100-353
Page

9

INSTALLATION

LOCATION

GENERAL

The unit must be located outside, or in a well ventilated
area.  It must not be in the space being heated or cooled.
A sound absorbing material should be considered if the
unit is to be installed in such a position or location that
might cause transmission of sound or vibration to the
living area or adjacent buildings.

SLAB MOUNTING

In areas where winter temperatures DO NOT go below
32° F for periods over twelve hours, the unit may be
slab mounted at grade level.  When installing unit at
grade level, install on a concrete slab at least four
inches above finished grade level.  Slab should have a
slope tolerance away from the building structure of at
lease 1/4 inch per foot, while being level from side to
side.  Place slab in a location where runoff water from
higher ground will not collect around unit.  See
Figure 2.

A minimum of 18 inches should be provided between
the coil inlet and any building surfaces.  Provide at least
four feet between coil outlet and any building wall,
fences or other vertical structures.  Provide a minimum
of three feet clearance on the service access side of the
unit.  See Figure 3.

ROOF MOUNTING

When a unit is installed in areas where low ambient
temperatures or strong winter winds exist, it should be
placed for prevailing winter winds are not in direct line
with the outdoor coil.  If this is not possible, a wind
barrier should be constructed.  Place barrier 24 inches
from the coil inlet side of the unit and in the direction
of prevailing winds.  Size barrier at least the same
height and width as the unit.  This may be necessary on
ground level installations, also.  See Figure 4.

WINTER INSTALLATION BELOW 32°F

In areas where winter conditions go below 32°F for
extended periods, the unit must be elevated above the
mounting surface to prevent snowfall or ice
accumulation from interfering with the operation of the
unit.  A minimum of twelve inch elevation is
recommended, while greater elevation may be required
for areas of high snow accumulation.  Poured concrete,
steel framework, brick, cement block, etc., can be
utilized to construct a suitable raised mounting
platform.  See Figure 5.

TYPICAL INSTALLATIONS

1.

ROOF MOUNTED

  –  The unit is mounted on a

sturdy base on the roof of the building.  Return air
to the unit is brought through a single return grille
(grilles with built-in filters are best since they
enable easy access for filter changing).  Return air
ducts are attached to the lower section of the front
panel.  Supply air is brought from the unit to attic
duct work or to a furred down hall.  Supply air duct
is attached to the top of the front panel.

CAUTION: All outdoor duct work must be

thoroughly insulated and weatherproofed.  All
attic duct work must be thoroughly insulated.
Two inch thick insulation with suitable vapor
barrier is recommended for both outdoor and
attic runs.

In roof top installation, as in all installations, the air
conditioner must be level from side to side.
However, the unit should have a pitch along the
length to assure complete external drainage of
precipitation and of defrost condensate.  See Figures
6 and 7, and Tables 6 and 7.

2.

CRAWL SPACE

  –  Duct work installed in crawl

space must be well insulated and provided with a
vapor barrier.  In addition, the crawl space must be
thoroughly ventilated and provided with a good
vapor barrier as a ground cover.  It is most desirable
to install the unit will be outdoors rather than inside
the crawl space, so that it will be readily accessible
for service.

3.

SLAB MOUNTED AT GROUND LEVEL

    This

type installation is ideal for homes with a slab floor
construction where a roof mounted unit is not
desired.  The supply and return duct work can be run
through a furred closet space.

4.

THROUGH THE WALL 

 –  This type installation

requires a suitable framework to be fabricated
capable of withstanding the unit weight.  Normally
the unit will be insulated so as to minimize supply
and return duct work.

Summary of Contents for P1124A3

Page 1: ...P1230A1 P1136A2 P1236A1 P1142A3 P1242A1 P1148A2 P1248A2 P1060A1 INSTALLATION INSTRUCTIONS Manual 2100 353D Supersedes 2100 353C File Volume II Tab 10 Date 03 19 03 Bard Manufacturing Company Bryan Ohi...

Page 2: ...sions 8 Figure 2 Slab Mounting at Ground Level 10 Figure 3 Airflow and Service Access Clearances 10 Figure 4 Roof Top Application 11 Figure 5 Elevated Mounting Platforms 11 Figure 6 Prefabricated Rood...

Page 3: ...and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Co...

Page 4: ...to the equipment While these instructions are intended as a general recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consult...

Page 5: ...e r p m o C l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S s t l o V 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 0 6 4 8 0 2 0 3 2 s p m A d a o L d e t a R 0 9 5 8 6 3 1...

Page 6: ...o s s e r p m o C l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S s t l o V 8 0 2 0 3 2 8 0 2 0 3 2 0 6 4 8 0 2 0 3 2 8 0 2 0 3 2 0 6 4 s p m A d a o L d e t a R 5 0 2 5 8 1 4...

Page 7: ...l o r c S l l o r c S l l o r c S l l o r c S s t l o V 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 s p m A d a o L d e t a R 0 9 5 8 8 2 1 4 1 1 2 6 1 3 4 1 9...

Page 8: ...0 4 2 A N S A N A N A N A N A N A N A N 5 1 A C P 3 H E 1 8 0 2 0 4 2 A N A N A N S A N A N A N S A N 9 0 B B P 3 H E 3 8 0 2 0 4 2 A A N A A N A S A A N S 5 1 B B P 3 H E 3 8 0 2 0 4 2 A N A N A A N...

Page 9: ...2 7 2 3 8 0 6 0 3 0 6 0 6 1 1 1 1 3 2 6 2 6 4 3 5 8 6 9 7 1 9 4 0 1 5 2 0 3 0 5 0 6 0 7 0 8 0 0 1 0 1 1 0 1 0 1 8 6 4 4 3 2 0 1 0 1 8 6 9 0 B B P 3 H E 5 1 B B P 3 H E 3 8 0 2 0 4 2 3 8 0 2 0 4 2 9 5...

Page 10: ...c n I g n i n e p O t c u D H e g r a h c s i D r i A n r u t e R A B C J K L M D E F G 3 A 4 2 1 1 P 2 A 4 2 2 1 P 2 A 0 3 1 1 P 1 A 0 3 2 1 P 2 A 6 3 1 1 P 1 A 6 3 2 1 P 4 1 4 2 6 1 3 8 4 8 1 8 3 8...

Page 11: ...ing with the operation of the unit A minimum of twelve inch elevation is recommended while greater elevation may be required for areas of high snow accumulation Poured concrete steel framework brick c...

Page 12: ...Manual 2100 353 Page 10 FIGURE 2 SLAB MOUNTING AT GROUND LEVEL Above 32 F Outside Temperature MIS 1184 FIGURE 3 AIRFLOW AND SERVICE ACCESS CLEARANCES MIS 1185...

Page 13: ...Manual 2100 353 Page 11 FIGURE 5 ELEVATED MOUNTING PLATFORMS MIS 1183 FIGURE 4 ROOF TOP APPLICATION May also be required for ground level installations MIS 1176...

Page 14: ...Manual 2100 353 Page 12 FIGURE 6 PREFABRICATED ROOF CURB SPECIFICATIONS HEAVY GAUGE GALVANIZED WITH WOOD NAILING STRIP WELDED LEAKPROOF ONCE PIECE CONSTRUCTION READY TO INSTALL MIS 1177C...

Page 15: ...P 1 A 2 4 2 1 P 2 A 8 4 1 1 P 2 A 8 4 2 1 P 1 A 0 6 0 1 P 0 6 E H R 4 0 0 2 4 0 9 5 7 3 2 8 5 2 1 4 4 5 2 1 1 4 5 7 3 8 3 5 7 3 5 3 4 4 5 2 1 3 5 2 1 9 1 0 5 5 7 4 1 2 4 5 2 8 3 j A SEPARATE METAL FLA...

Page 16: ...AIR FILTERS Air filters for the return air side of the system are not provided as part of these models and must be field supplied and installed as part of the final installation Prior thought should b...

Page 17: ...th the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor WIR...

Page 18: ...Manual 2100 353 Page 16 FIGURE 9 LOW VOLTAGE WIRING MIS 1180...

Page 19: ...tarting the compressor and outdoor motor The G indoor motor circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air ci...

Page 20: ...rm signal is desired This terminal is powered whenever compressor is locked out due to HPC or LPC sequences as described NOTE Both high and low pressure switch controls are inherently automatic reset...

Page 21: ...mperative to match the correct pressure table to the unit by model number REFRIGERANT CHARGE The correct system R 22 charge is shown on the unit rating plate Optimum unit performance will occur with a...

Page 22: ...ormly around the circumference to flow braze material completely around the joint Slowly move torch into Area 3 to draw braze material into joint See Figure 11 Do not overheat joint MIS 1179 FIGURE 11...

Page 23: ...5 2 2 1 8 0 4 2 2 8 0 6 2 4 8 8 7 2 5 8 5 9 2 6 8 5 1 3 7 8 5 3 3 8 8 1 5 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 4 8 2 1 2 6 8 3 3 2 7 8 8 4 2 8 8 9 6 2 0 9 7 8 2 1 9 5 0 3 2 9 6...

Page 24: ...d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 3 7 3 0 2 4 7 8 1 2 5 7 1 3 2 6 7 6 4 2 8 7 4 6 2 9 7 8 7 2 0 8 4 9 2 1 8 2 1 3 2 8 0 3 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 8...

Page 25: ...k c e h C d e e p s M F C h g i h t a s f f u p r o s t n u H g n i f f u p e c u d e r r e t l i f r o l e n a p g n i v o m e r s e o D n o i t c i t s e r e c u d e R w o l f r i a m u m i x a m e...

Page 26: ...w s c a i r T r o f k c e h C y a l e r N O T P M Y S E R U D E C O R P E S U A C e s i o n e v i s s e c x E e s i o n r o t o m r o t c u d t e n i b a c e s i o n r i a s i t i f i e n i m r e t e...

Page 27: ......

Page 28: ......

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ......

Page 33: ......

Page 34: ......

Page 35: ......

Reviews: