Manual 2100-676D
Page
29 of 45
FIGURE 20
Placement of Communication Wire Filters (Daisy Chain and Alternate Methods)
LC6000
... up to 14 units
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
* LC6000 can be in any position other than start and end
Place filter here
Place filter here
(end unit)
LC6000*
Unit 1
Unit 2
... up to 14 units
Unit 3
Unit 4
Unit 5
Place filter here
(end unit)
Daisy Chain Wiring
Alternate Wiring
Place filter here
(end unit)
NOTE:
Line filters can be on either the unit or controller, whichever device is on the end of the chain. No matter
how many units there are, the two end devices will only have ONE communication cable, whereas the
center devices will all have TWO (as shown above). Maximum two wires in each terminal. Filters go inside
the unit or controller; shown out of unit above for identification only.