![background image](http://html1.mh-extra.com/html/bard/mc500-series/mc500-series_installation-and-operation-instructions-with-replacement-parts-list_3898830037.webp)
Manual 2100-746D
Page
35 of 59
FIGURE 16
Back of Touch Screen Display
1. Ethernet Reset – Pressing the Ethernet Reset button will revert all IP settings back to the
factory default settings.
NOTE:
Hold button for minimum of 10 seconds to activate reset.
2. REM U/D Jumper – With this jumper in place, updating of firmware is allowed. In the
event this jumper is ever removed, place it onto one of the pins to prevent loss where it
will be available if it becomes necessary to re-install it at a later date.
3. Shield/GND Jumper – Removing this jumper isolates the shielding around the Ethernet
port from the network ground. It is recommended to leave the jumper in place unless
issues with the network ground occur.
4. System Reset – Pressing the System Reset button will reset the display and retain the
system settings.
CAUTION:
The System Reset button has an immediate response.
5. SD Card Slot – The SD card must be a micro SD card (FAT format only).
MIS-4194 A
SD CARD
SLOT
REM U/D
SHIELD GND
SYS RESET
ETHERNET
SYSTEM RESET
ETHERNET RESET
RESET
USE CR2032
SHIELD GROUND
8612-065
REM U/D
JUMPER
MIS-4194A
FIGURE 17
Setup Button on MC5000 Series Home Screen
Webpage IP Configuration
NOTE:
If the initial network settings configuration
are to be done via the webpage, an Ethernet
patch cable will need to be connected to the
controller and the default addressing will need
to be used (see Table 5).
Once the webpage has loaded, press on the Network
Configuration tab in the navigational pane (see Figure
18 on page 36). This will open up two additional
tabs, IPv4 Configuration and IPv6 Configuration. Click
the appropriate tab for configuration page.