TROUBLESHOOTING INDOOR ECM™ BLOWER MOTORS 

(Cont’d.)

Replacing ECM Control Module

To replace the control module for the GE variable-speed indoor blower
motor you need to take the following steps:

1. You MUST have the correct replacement module.  The controls are

factory programmed for specific operating modes.  Even though they look
alike, different modules may have completely different functionality.

USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT
WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.

2. Begin by removing AC power from the unit being serviced.  

DO NOT

WORK ON THE MOTOR WITH AC POWER APPLIED.  

To avoid

electric shock from the motor’s capacitors, disconnect power and wait at
least 5 minutes before opening motor.

3. It is not necessary to remove the motor from the blower assembly, nor

the blower assembly from the unit.  Unplug the two cable connectors to the
motor control assembly.  There are latches on each connector.  

DO NOT

PULL ON THE WIRES.  

The plugs remove easily when properly

released.

4. Locate the screws that retain to the motor control bracket to the

sheet metal of the unit and remove them.  Remove two (2) nuts that
retain the control to the bracket and then remove two (2) nuts that
retain sheet metal motor control end plate.  

Refer to Figure 24.

5. Disconnect the three (3) wires interior of the motor control by

using your thumb and forefinger squeezing the latch tab and the
opposite side of the connector plug, gently pulling the connector.  

DO

NOT PULL ON THE WIRES, GRIP THE PLUG ONLY.  

Refer to

Figure 24.

6. The control module is now completely detached from the motor.

Verify with a standard ohmmeter that the resistance from each motor
lead (in the motor plug just removed) to the motor shell is >100K
ohms.  

Refer to Figure 25.  

(Measure to unpainted motor end plate.)  If

any motor lead fails this test, do not proceed to install the control
module.  

THE MOTOR IS DEFECTIVE AND MUST BE

REPLACED.

  Installing the new control module will cause it to fail

also.

7. Verify that the replacement control is correct for your

application.  Refer to the manufacturer's authorized replacement list.

USING THE WRONG CONTROL WILL RESULT IN
IMPROPER OR NO BLOWER OPERATION.

  Orient the control

module so that the 3-wire motor plug can be inserted into the socket in
the control.  Carefully insert the plug and press it into the socket until
it latches.  

A SLIGHT CLICK WILL BE HEARD WHEN

PROPERLY INSERTED.

8. Reverse the steps #5, 4, 3 to reconnect the motor control to the

motor wires, securing the motor control cover plate, mounting the
control to the bracket, and mounting the motor control bracket back
into the unit.  

MAKE SURE THE ORIENTATION YOU SELECT

FOR REPLACING THE CONTROL ASSURES THE
CONTROL'S CABLE CONNECTORS WILL BE LOCATED
DOWNWARD IN THE APPLICATION SO THAT WATER
CANNOT RUN DOWN THE CABLES AND INTO THE
CONTROL.

  DO NOT OVERTIGHTEN THE BOLTS.

9. Plug the 16-pin control plug into the motor.  The plug is keyed.

Make sure the connector is properly seated and latched.

10. Plug the 5-pin power connector into the motor.  Even though

the plug is keyed, 

OBSERVE THE PROPER ORIENTATION.  DO

NOT FORCE THE CONNECTOR.

  It plugs in very easily when

properly oriented.  

REVERSING THIS PLUG WILL CAUSE

IMMEDIATE FAILURE OF THE CONTROL MODULE.

11. Final installation check.  Make sure the motor is installed as follows:

a. Motor connectors should be oriented between the 4 o’clock

and 8 o’clock positions when the control is positioned in its
final location and orientation.

b.Add a drip loop to the cables so that water cannot enter the

motor by draining down the cables.  

Refer to Figure 26.

The installation is now complete.  Reapply the AC power to the
HVAC equipment and verify that the new motor control module is
working properly.  Follow the manufacturer's procedures for
disposition of the old control module.

Motor

Motor OK when

R > 100k ohm

ECM 2.0

Only remove

Hex Head Bolts

Connector Orientation

Between 4 and 8 o'clock

Drip Loop

Back of

Control

Figure 5

Winding Test

Figure 4

Note:              
Use the shorter 
bolts and 
alignment pin 

supplied when 
replacing an 

ECM 2.0 
control.

Figure 3

ECM 

2.3/2.5

Power Connector
(5-pin)

Control Connector
(16-pin)

Hex-head Screws

Motor Connector
(3-pin)

Motor Connector
(3-pin)

Control Disassembly

Drip Loop

Push until

Latch Seats
Over Ramp

From Motor

Circuit

Board

Figure 25

Figure 24

Figure 26

Summary of Contents for I-TEC I30A1D

Page 1: ...I42A1D I48A1D I60A1D I TEC SERIES PACKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 597 Supersedes...

Page 2: ...tor 48 49 Fan Blade Setting Dimensions 50 Refrigerant Charge 50 Figures Figure 1 Unit Dimensions 7 Figure 2A Unit on Lift 8 Figure 2B Unit Side 8 Wall Mounting Bracket Location 9 Bracket Wall Sect Vie...

Page 3: ...mer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Condition...

Page 4: ...ation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Systems of Other Than...

Page 5: ...oated Alum Cond Coil 1 Phenolic Coated ID Coil 2 Phenolic Coated OD Coil 3 Phenolic Coated ID OD Coil CONTROLS X 24V Terminal Block Only w o CompleteStat 1 CompleteStat THO Temp Humidity Occupancy 2 C...

Page 6: ...0 C 5 1 C 3 0 6 4 1 1 1 1 2 1 4 1 9 1 8 2 5 1 5 1 0 2 0 3 4 1 4 1 2 1 0 1 4 1 4 1 2 1 0 1 Z 0 A D 1 A 8 4 I 4 0 A 5 0 A 0 1 A 5 1 A 0 2 A 1 8 0 2 0 3 2 1 1 1 1 2 r o 1 2 r o 1 4 3 4 3 4 3 9 5 5 8 0 1...

Page 7: ...5 47 3 46 1 8 With Sides Removed Vent Intake Disconnect Electrical Air Filters Vent Exhaust Door Latch Locking Filters Return Air 2 12 x 20 Door Latch Locking Air Filters 2 Washable Hinges 4 Lift Off...

Page 8: ...tempt to do this manually Failure to do so could result in the unit tipping over causing bodily injury and or damage to the unit 7 The top section can be forked from either the RH or LH side See Figur...

Page 9: ...a built in vertical adjustment to fit window sill heights from 31 34 inches If additional height is required two riser platform accessories are available The IRP3 increases the unit height by 3 inche...

Page 10: ...nting holes Mounting holes 4 optional Unit Wall Opening Sleeve Mounting Hole Locations Optional Top Bracket 7 32 29 1 8 56 8 6 7 20 20 17 8 2 8 20 7 8 42 3 4 Min 16 8 11 16 15 20 94 34 Max 31 Min Cent...

Page 11: ...e m i D X n o i s n e m i D Y n o i s n e m i D Z n o i s n e m i D Z B D A D 1 A 0 3 I 4 3 3 1 4 2 3 4 7 4 C D 1 A 0 3 I 4 3 3 1 4 2 3 4 7 4 B D A D 1 A 6 3 I 4 3 3 1 4 2 3 4 7 4 C D 1 A 6 3 I 4 3 3...

Page 12: ...Manual 2100 597 Page 12 of 52 FIGURE 3 COMPRESSOR SHIPPING BOLTS FIGURE 4 REMOVAL OF AIR DUCT COMPRESSOR SHIPPING BOLT COMPRESSOR SHIPPING BOLT CRV ERV AIR DUCT...

Page 13: ...NDED TO BOTTOM OF ROOF 9 7 MINIMUM OR FIXED CEILING FLOOR OR FIXED CEILING BOTTOM OF ROOF SUSPENDED CEILING 20 MINIMUM 7 9 3 4 UNIT HEIGHT FIELD SUPPLIED DUCT TURNING VANES RECOMMENDED MINIMUM 12 4 MI...

Page 14: ...NDED TO BOTTOM OF ROOF 9 10 MINIMUM OR FIXED CEILING 3 RISER FIELD SUPPLIED DUCT TURNING VANES RECOMMENDED 12 MINIMUM 4 MINIMUM FROM TOP OF UNIT TO DUCT BOTTOM MIS 2989 B FLOOR OR FIXED CEILING BOTTOM...

Page 15: ...XED CEILING 6 RISER 9 8 MINIMUM REQUIRED INSTALLATION HEIGHT BOTTOM OF ROOF FLOOR OR FIXED CEILING SUSPENDED CEILING MINIMUM 20 7 9 3 4 UNIT HEIGHT FIELD SUPPLIED DUCT MIS 2988 B TURNING VANES RECOMME...

Page 16: ...DF Plenum Box mounts on top of the unit and has both vertically and horizontally adjustable louvers on the front discharge grille When used with a ducted supply an ICX28 Cabinet Extension may be used...

Page 17: ...t about 12 inches in from the front on both the left and right side are drain holes in the bottom of the base These holes are covered with insulation and are not visible They are located very close to...

Page 18: ...k bead to Apply liberal amount of caulk to back of flange before installing Use 4 1 1 2 Long Screws to Sleeve Attach Louver Grille to Outer Unit Fan Shroud to Outer Sleeve to Unit Back to Attach Inner...

Page 19: ...Manual 2100 597 Page 19 of 52 INTERIOR FLOOR I TEC UNIT OUTSIDE WALL FILL INSULATION FILL INSULATION OUTDOOR GRILLE SIZE VARIES INSIDE WALL SLEEVE MIS 2928 A FIGURE 9B UNIT MOUNTING...

Page 20: ...nformation and maximum fuse or HACR Type circuit breaker size Each unit is marked with a Minimum Circuit Ampacity This means that the field wiring used must be sized to carry that amount of current De...

Page 21: ...e v o e g n a h c l a u n a M r o o t u A 7 6 0 3 0 4 8 Y L R D C L 0 4 W 2 T D C r o f D C L h t i w r o s n e S e d i x o i D n o b r a C s g n i d a e R r o s n e S O H T B 9 S C v n o C r o P H g...

Page 22: ...e Term Strip R 3 SC W1 E A D L O B Y2 Y1 24V G COM W2 Completestat Model CS9B THO or Model CS9BE THO SC SC Thermostat W1 E A YO D L O B Y2 Y1 R G C W2 Bard 8403 060 2 1 Additional wire required for de...

Page 23: ...L O B Y2 Y1 R G C W2 Bard 8403 060 BLACK WHITE ORANGE BROWN WHITE 1 Additional wire required for dehumidification models 2 Not needed below 15KW 3 to N C fire alarm circuit if emergency shutdown requ...

Page 24: ...d jumper Remove jumper and connect 4 Connect to G terminal when thermostat has Occupancy Signal 6 without Occupance Signal is used Install a jumper between G and A only when thermostat 5 4 5 CRV Wirin...

Page 25: ...ACK WHITE ORANGE 1 Additional wire required for dehumidification models 2 Not needed below 15KW 3 to N C fire alarm circuit if emergency shutdown required Factory installed jumper Remove jumper and co...

Page 26: ...mper Remove jumper and connect 4 Connect to G terminal when thermostat has Occupancy Signal 6 without Occupance Signal is used Install a jumper between G and A only when thermostat 5 4 5 ERV Wiring Ha...

Page 27: ...below 15KW to N C fire alarm circuit if emergency shutdown required Factory installed jumper Remove jumper and connect 2 3 2 4 Connect to G terminal when thermostat has Occupancy Signal without Occup...

Page 28: ...ng multiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system...

Page 29: ...the power Since there is a 50 50 chance of connecting power in such a way as to cause rotation in the reverse direction verification of proper rotation must be made Verification of proper rotation di...

Page 30: ...heat completes R Y1 circuit pulling in compressor contactor starting compressor and outdoor motor R G also make starting indoor blower motor HEATING STAGE 2 Circuit R Y1 Y2 makes at the thermostat en...

Page 31: ...lectronic thermostat with auxiliary terminal to control the CRV based on daily programmed occupance periods Bard markets and recommends Bard Part 8403 060 programmable electronic thermostat 2 Use Bard...

Page 32: ...OPTION INTAKE EXHAUST SPEEDS BROWN WHITE BLACK BLUE ORANGE NOM CFM BLACK BLUE WIRE COLOR SPEED RED WIRE WITH WHITE TRACE 300 375 450 525 LO MED LO MED HI HI RED Move brown white wire to corresponding...

Page 33: ...CRV SPEED CHANGE TERMINAL ACCESS REMOVE 5 SCREWS FROM CRV DOOR TO ACCESS CRV COMPONENTS MIS 3023 CRV INTAKE BLOWER NOTE CRV EXHAUST BLOWER IS BEHIND INTAKE BLOWER BLOWER SPEED CONTROL LOCATION BLOWER...

Page 34: ...erature freezing of moisture in the heat transfer wheel can occur Consult the factory if this possibility exists The I TEC ERV can be controlled in different ways It can be turned ON OFF with an occup...

Page 35: ...re Then perform the following steps 1 Open front swinging doors of main unit by popping front door latches 2 Throw main power disconnect to the OFF position to eliminate risk of injury or death due to...

Page 36: ...0 5 9 0 8 0 9 5 1 3 0 2 7 9 0 7 8 1 2 3 3 5 0 2 8 1 3 6 5 1 2 4 1 5 2 3 6 2 0 0 1 8 5 2 2 8 1 4 7 3 7 1 5 4 3 5 8 2 0 2 1 0 6 0 1 2 0 8 4 6 0 8 5 4 1 0 1 1 4 1 1 4 3 4 8 6 7 9 5 7 5 6 4 1 2 0 2 7 9 4...

Page 37: ...ng blinks for the TEN COUNT of the FLOW RATE INDEX which then is immediately followed by fast blinks which indicate the second digit For example a Flow Index of 23 would be two long blinks followed by...

Page 38: ...Manual 2100 597 Page 38 of 52 FIGURE 20 VENTILATION AIRFLOW DIAGRAM EXHAUST Return Air Indoor Air VENT Outdoor Air BLOWER BLOWER INTAKE Supply Air VENT SUPPLY BLOWER MIS 3024...

Page 39: ...Page 39 of 52 FIGURE 21 ERV ACCESS ERV DOOR TO ACCESS ERV COMPONENTS ASSEMBLIES REMOVE 5 SCREWS FROM PANEL LOCATION MIS 3025 ERV CONTROL ERV CASSETTE NOTE ERV EXHAUST BLOWER IS BEHIND INTAKE BLOWER ER...

Page 40: ...quipment damage Make sure all connections are in accordance with the job wiring diagram and in accordance with national and local electrical codes Use copper conductors only Use electrostatic discharg...

Page 41: ...ure below Finish installing wiring the control Then refer to Figure 19 and the building ventilation specifications to decide what the maximum ventilation rate desired is and what the minimum maximum v...

Page 42: ...2 low output range Sets the CO2 concentration for the lowest output 4 mA or 0 VDC Low limit 0 PPM Factory setting 0 PPM High limit 2000 5000 PPM depending on model COH CO2 high output range Sets the C...

Page 43: ...to remove oils grease tars and dirt that can impede performance or generate odors Washing of the desiccant surfaces is required to remove contaminate buildups that can reduce adsorption of water molec...

Page 44: ...based cleaners aromatic solvents temperatures in excess of 170 F or steam Damage to the wheel may result Do not disassemble and immerse the entire heat wheel in a soaking solution as bearing and othe...

Page 45: ...5 5 0 4 6 3 5 1 5 0 2 5 4 1 5 0 5 8 2 0 9 4 0 9 5 4 1 0 0 2 6 4 5 5 8 4 4 4 5 5 3 4 5 9 2 2 4 7 7 0 1 4 8 9 8 9 3 7 5 7 8 3 2 5 6 7 3 3 8 5 6 3 8 4 5 5 3 5 4 5 4 3 4 7 5 3 3 4 3 6 2 3 3 2 7 1 3 0 4 8...

Page 46: ...it is tight on the motor shaft Also ensure the motor is secure in its mounting system and the mounting system is secure to the unit c The Bard I TEC is equipped with a low ambient control pressure swi...

Page 47: ...er that is a direct replacement for the failed motor USING THE WRONG MOTOR VOIDS ALL PRODUCT WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS Always mount the replacement motor and control according to t...

Page 48: ...e if it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down...

Page 49: ...Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted...

Page 50: ...TOR MOTOR HALF R O T C E N N O C R E W O P R E D A E H B W P 0 5 4 9 0 5 3 1 P M A N I P n o i t p i r c s e D 1 r o f 2 n i P o t 1 n i P r e p m u J t u p n I e n i L C A V 0 2 1 y l n O 2 3 d n u o...

Page 51: ...1 9 9 2 0 3 1 9 1 3 1 3 1 9 3 3 3 3 1 0 6 3 4 3 1 0 8 3 5 3 1 4 0 4 6 3 1 8 2 4 7 3 1 2 5 4 8 3 1 6 7 4 9 3 1 0 0 5 0 4 1 4 2 5 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 4 3 1 7 1 2 6 3 1 9 3 2 8...

Page 52: ...1 4 7 2 6 3 1 4 9 2 8 3 1 5 1 3 9 3 1 5 3 3 1 4 1 6 5 3 2 4 1 9 7 3 3 4 1 2 0 4 4 4 1 6 2 4 5 4 1 9 4 4 6 4 1 2 7 4 7 4 1 6 9 4 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 0 4 1 5 9 1 1 4 1 6 1 2 3...

Reviews: