Manual 2100-568A
Page
9 of 23
fiGure 4
electric heat clearance
h42a1, h42l1, h48a1, h48l1, h60a1, h60l1
WarninG
A
minimum
of 1/4 inch clearance must be maintained between
the supply air duct and combustible materials. This is required for
the first 3 feet of ducting.
It is important to insure that the 1/4 inch minimum spacing is
maintained at all points.
Failure to do this could result in overheating the combustible
material and may result in a fire causing damage, injury or death.
nOte 1
: SIDE SECTION VIEW OF SUPPLY AIR
DUCT FOR WALL MOUNTED UNIT SHOWING 1/4
INCH CLEARANCE TO COMBUSTIBLE SURFACES.