Manual 2100-568A
Page 20 of 23
table 5
recOmmended airflOW
table 6
indOOr blOWer PerfOrmance
table 7
maXimum esP Of OPeratiOn
electric heat OnlY
Values shown are for units equipped with standard 1-inch throwaway filter or 1-inch washable filter.
Derate ESP by .15 for 2-inch pleated filters.
model
rated
cfm *
rated
esP *
recommended
Airflow Range
factory speed
connection
H42A, H42L
1400
.30
1600 - 1150
High
H48A, H48L
1550
.20
1750 - 1285
High
H60A, H60L
1650
.30
1950 - 1375
High
e.s.P.
in
h2O
h42a/l, h48a/l
h60a/l
high speed
low speed
high speed
low speed
dry
coil
Wet
coil
dry
coil
Wet
coil
dry
coil
Wet
coil
dry
coil
Wet
coil
.0
.1
.2
.3
.4
.5
1885
1770
1635
1500
1370
1250
1800
1665
1540
1400
1285
1150
1650
1550
1450
1350
1300
—
1600
1500
1400
1300
1175
—
2200
2100
2000
1875
1775
1650
2000
1900
1800
1700
1600
1475
1600
1525
—
—
—
—
1450
1375
—
—
—
—
model
h42a/l, h48a/l
h60a/l
Outlet
frOnt
frOnt
speed
high
low
high
low
-A0Z
-A05
-A10
-A15
-A20
.50
.50
.50
.50
.50
.50
.50
.50
.50
.45
.50
.50
.50
.50
.50
.50
.50
.50
.50
.40
-B0Z
-B09
-B15
-B18
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
-C0Z
-C09
-C15
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
.50
* Rated CFM and ESP on high speed tap.