background image

Manual 2100-647D 

Page 

18 of 36

HIGH PRESSURE AND LOW PRESSURE 

SWITCHES

All H**A/H**L wall mounted air conditioner series 
models are supplied with a remote reset for the high 
and low pressure switches.  The first time the high 
or low pressure switches are tripped, they will reset 
automatically. If tripped a second time, reset the 
switches by turning the thermostat off, then back on 
again, resetting the compressor control module. 

THREE PHASE SCROLL COMPRESSOR 

START UP INFORMATION

Scroll compressors, like several other types of 
compressors, will only compress in one rotational 
direction.  Direction of rotation is not an issue with 
single phase compressors since they will always start 
and run in the proper direction.

However, three phase compressors will rotate in either 
direction depending upon phasing of the power.  
Since there is a 50-50 chance of connecting power 
in such a way as to cause rotation in the reverse 
direction, verification of proper rotation must be made.  
Verification of proper rotation direction is made by 
observing that suction pressure drops and discharge 
pressure rises when the compressor is energized.  
Reverse rotation also results in an elevated sound level 
over that with correct rotation, as well as substantially 
reduced current draw compared to tabulated values.

Verification of 

proper rotation

 must be made at the time 

the equipment is put into service.  If improper rotation 
is corrected at this time, there will be no negative 
impact on the durability of the compressor. However, 
reverse operation for over 1 hour may have a negative 
impact on the bearing due to oil pump out.

NOTE:

  If compressor is allowed to run in reverse 

rotation for an extended period of time, the 

compressor’s internal protector will trip.

All three phase compressors are wired identically 
internally.  As a result, once the correct phasing 
is determined for a specific system or installation, 
connecting properly phased power leads to the same 
Fusite terminal should maintain proper rotation 
direction.

The direction of rotation of the compressor may be 
changed by reversing any two line connections to the 
unit.

PHASE MONITOR

All units with three phase scroll compressors are 
equipped with a three phase line monitor to prevent 
compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two 
LEDs.  If the Y signal is present at the phase monitor 
and phases are correct, the green LED will light.

If phases are reversed, the red fault LED will be lit and 
compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply 
leads to the unit.  

Do not reverse any of the unit factory 

wires as damage may occur.

CONDENSER FAN OPERATION

NOTE: These models are equipped with a low ambient 

control (LAC).  The condenser fan motor may have a 

delayed start until system refrigerant operating pressure 

builds up.  After starting, the fan motor may or may 

not cycle depending upon ambient conditions.  This 

is normal operation.

  The condenser fan motor on 

230/208 volt, one and three phase, 60 HZ units is 
a two-speed motor that comes factory wired on high 
speed for peak performance.  If ambient conditions 
permit, it can be reconnected to low speed (red wire) 
for lower sound level.  See unit wiring diagram.  

SERVICE HINTS

1.  Caution owner/operator to maintain clean air filters 

at all times and to not needlessly close off supply 
and return air registers.  This reduces airflow 
through the system, which shortens equipment 
service life as well as increasing operating costs.

2.  Check all power fuses or circuit breakers to be sure 

they are the correct rating.

3.  Periodic cleaning of the outdoor coil to permit full 

and unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

COOLING – 24VAC from MV controller at terminal 4 (Y)
pulls in compressor contactor, starting the compressor 
and outdoor motor.  (See 

NOTE

 under Condenser 

Fan Operation concerning the low ambient control.)  
Terminal 9 (G) indoor motor circuit is energized by 
the MV controller on any call for cooling operation or 
can be energized by manual fan switch on subbase for 
constant air circulation.  A call for heating from the MV 
controller pulls in heat contactor, activating the strip 
heat and blower operation.  On a call for second stage 
heat, R-W2 makes bringing on second heat contactor, 
if so equipped.  See Table 1 on following page.

COMPRESSOR CONTROL MODULE

The compressor control module (CCM) is standard on 
all models covered by this manual.  The compressor 
control module is an anti-short cycle/lockout timer with 
high and low pressure switch monitoring and alarm 
relay output.

Summary of Contents for H12AA-A

Page 1: ...H12AA A H24AA A H36AA A H42AA A H48AA A H60AA A H72AA A H24LA A H36LA A H42LA A H48LA A H60LA A H72LA A Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 647D Supersedes 210...

Page 2: ...Blower Performance 25 Table 7 Max ESP of Operation Elec Heat Only 25 Table 8A H12 Electric Heat 26 Table 8B H24 72 Electric Heat 26 Table 9 Optional Accessories 27 Table 10 Vent and Control Options 2...

Page 3: ...ummer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contract...

Page 4: ...ed before the installation is made See page 3 for information on codes and standards Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air...

Page 5: ...be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Some installations may not require any return air duct A metallic return air grille is required with in...

Page 6: ...olts 7 Secure rain flashing to wall and caulk across entire length of top see Figures 3A D 8 For additional mounting rigidity the return air and supply air frames or collars can be drilled and screwed...

Page 7: ...63 CONDENSER AIR OUTLET HEATER FILTER ACCESS AIR VENTILATION CONDENSER AIRFLOW IS BLOW THRU 19 72 3 88 31 06 19 72 20 43 SHIPPING LOCATION ENTRANCE ELECTRICAL OPTIONAL TOP RAIN FLASHING DRAIN HOSE 22...

Page 8: ...d Entrance Air Panel Drain Heater Disconnect Entrance 4 Pitch Inlet Access Panel Economizer Rain Hood Low Voltage Electrical Air Intake Hood C Breaker High Voltage Economizer Controls H A D J C I 2 13...

Page 9: ...SUPPLIED FOAM AIR SEAL WALL WALL STRUCTURE MIS 3600 FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION SUPPLY AIR DUCT RETURN AIR NOTE IT IS RECOMMENDED THAT A BEAD OF SILICONE CAULKING BE PLACED...

Page 10: ...F TOP TOP WALL OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE OPENING TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER DUCT Wall Opening and Hole Location View Right Side...

Page 11: ...4 CLEARANCE ON ALL HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICONE CAULKING BE PLACED BEHIND IS ON OPPOSITE LEFT SIDE OPENING CONTROLS AND HEATER ACCESS...

Page 12: ...1 4 1 1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM...

Page 13: ...als This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the combustible materi...

Page 14: ...TURN AIR SUPPLY AIR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH...

Page 15: ...e that there will be no nuisance tripping due to the momentary high starting current of the compressor motor The disconnect access door on this unit may be locked to prevent unauthorized access to the...

Page 16: ...eplace filter 4 Press Reset button 5 Verify filter light is off 6 Replace filter door 7 Turn on unit power For units equipped with economizer 1 Turn off unit power 2 Remove hood cover 3 Remove mist el...

Page 17: ...nt composition during multiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant ch...

Page 18: ...d with a three phase line monitor to prevent compressor damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases...

Page 19: ...wer resets the manual lockout Alarm Relay Output Alarm terminal is the output connection for applications where an alarm relay is employed This terminal is powered whenever the compressor is locked ou...

Page 20: ...nds DOB 144 second DOM 5 0 minute 300 seconds DOB 150 second DOM During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay Typical Settings f...

Page 21: ...rge quantity The pressure table on the following page shows nominal pressures for the units Since many installation specific situations can affect the pressure readings this information should only be...

Page 22: ...38 587 80 67 Low Side High Side 125 331 128 355 130 379 133 404 136 430 138 457 140 485 143 513 145 542 147 572 148 602 85 72 Low Side High Side 129 343 132 367 135 392 138 418 141 445 143 473 145 502...

Page 23: ...Ckt C Ckt A Ckt B Ckt C H12AA A0Z A03 A05 230 208 1 1 1 1 9 20 27 15 20 30 14 12 10 14 12 10 H24AA A00 A0Z A04 A05 A08 A10 230 208 1 1 1 1 1 1 21 25 30 46 56 30 30 30 50 60 10 10 10 8 6 10 10 10 10 1...

Page 24: ...8 6 3 10 10 10 8 60 26 60 30 6 10 10 10 H60LA B00 B0Z B03 B05 B09 B15 230 208 3 1 1 1 1 1 27 27 27 35 53 40 40 40 40 60 8 8 8 8 6 10 10 10 10 10 H72LA A00 A0Z A05 A10 A15 230 208 1 1 1 1 1 or 2 58 58...

Page 25: ...5 2010 1965 1950 1870 0 2 425 400 905 870 1265 1185 905 890 1820 1760 1615 1565 1820 1770 1600 1540 1970 1885 1400 1315 2115 2035 1960 1915 1885 1825 0 3 375 360 835 800 1180 1100 860 850 1735 1665 15...

Page 26: ...7 13650 14 4 10240 5 20 8 17540 18 1 13275 12 0 17065 10 4 12799 6 14 4 20500 12 5 15360 8 33 3 27300 28 8 20475 9 21 7 30600 18 7 23030 10 41 6 34130 36 2 25600 15 62 5 51250 54 0 38400 36 2 51200 3...

Page 27: ...A A05 X X EHW6TA B03 X EHW6TA B06 X EHW72A A10B X EHW72A A15B X EHW72A A20B X Circuit Breakers WMCB Pull Disconnects WMPD WMCB 03A X WMCB 05A X WMCB 08A X X WMCB 09A X X Left Hand Units H24LA A H36LA...

Page 28: ...A X BOP 2 Blank Off Plate X EWM1 E EWM1 T Economizer Bldg Equipment Enthalpy Economizer Bldg Equipment DB Temp X X EWM2 E EWM2 T Economizer Bldg Equipment Enthalpy Economizer Bldg Equipment DB Temp X...

Page 29: ...Closed Dry Contacts MV Signals Blade Switch Fail Alarm 8 on Relay Board 8 13 Blade Switch Delay Relay Normally Closed Dry Contacts MV Signals Blade Switch Fail Alarm 9 on Relay Board 9 14 Occupied Sig...

Page 30: ...Contacts Not Used 4 11 Filter Switch Normally Closed Dry Contacts Not Used 5 12 Blade Switch Delay Relay Normally Closed Dry Contacts Not Used 8 13 Blade Switch Delay Relay Normally Closed Dry Contac...

Page 31: ...22 21 6 Circuit Breaker 30 Low Press Control Hi Press Control Black Black Black Black White Blk Wht Black White Black White Black White Condenser Section Module Alarm Relay Indoor Delay Blower Relay F...

Page 32: ...hite Black White Black White Heat Plug SMOKE JUMPER G LOUT 20 104 Condenser Section 6 Pin Electric Module Compressor Relay Alarm Relay Delay Blower Relay Indoor Relay Filter Switch Filter Reset Button...

Page 33: ...1 12 13 4 8 18 6 33 20 104 14 109 2 110 16 111 11 112 3 113 9 117 7 118 21 116 5 121 19 136 Dual Can Capacitor LOUT 5 ECON LOUT DAMPER 128 103 B 128 3 Black White Light 113 124 Terminal Black Black B...

Page 34: ...116 Black White 121 6 131 134 128 128 124 132 Black White 132 Light 23 32 10 Black White Black Black Black White 6 5 4 3 2 1 Blk Wht Black White Black White Black White Heat Plug Condenser Section 6...

Page 35: ...2 NC 3 2 1 NO 12 PIN PLUG COM DAMPER MOTOR DAMPER BLADE IN RED BLACK BLACK IS SHOWN WITH THE CONTACT POSITION IAQ AUX1 O Y2 I 8 S BUS ACT 24V ACT RED YELLOW IAQ R MAT PLUG PLUG PLUG PLUG BROWN WHITE G...

Page 36: ...n Vent Plug Pin 2 on Vent Plug Pin 5 on Vent Plug Pin 7 on Vent Plug Pin 10 on Vent Plug Time Delay Relay T1 T2 Y HPC Lo Press Sw LPC LPC Alarm Relay ALR CC Comp Control Module R MV Controller C 4 5 W...

Reviews: