Manual 2100-647D
Page
21 of 36
SERVICE
REMOVAL OF FAN SHROUD
1. Disconnect all power to the unit.
2. Remove screws holding both grilles, one on each
side of unit, and remove grilles.
3. Remove screws holding fan shroud to condenser
coil and unit base.
4. Disconnect condenser fan motor from control panel
wiring.
5. Slide complete motor, fan blade and shroud
assembly out appropriate side of the unit
(dependent on whether it is a right hand or left
hand unit).
6. Service motor/fan as needed.
7. Reverse steps to re-install
.
Make sure fan blade
setting dimension is checked and re-adjusted if
necessary.
R-410A REFRIGERANT CHARGE
This unit was charged at the factory with the quantity
of refrigerant listed on the serial plate. AHRI capacity
and efficiency ratings were determined by testing with
this refrigerant charge quantity.
The pressure table on the following page shows
nominal pressures for the units. Since many
installation specific situations can affect the pressure
readings, this information should only be used by
certified technicians as a guide for evaluating proper
system performance. They shall not be used to adjust
charge. If charge is in doubt, reclaim, evacuate and
recharge the unit to the serial plate charge.
FIGURE 8
Fan Blade Setting
"A"
AIRFLOW
MIS-1724
TABLE 2
Fan Blade Dimension
Model
Dimension
A
H12
2.25"
H24
1.00"
H36
1.25"
H42
H48
H60
H72
1.75"
FAN BLADE SETTING DIMENSIONS
The correct fan blade setting for proper air delivery
across the outdoor coil is shown in Figure 8. Refer to
Table 2 for unit specific dimension. Dimension "A" is
the distance between the closest point on fan blade to
motor mount leg.
Any service work requiring removal or adjustment in the
fan and/or motor area will require that the dimensions
below be checked and blade adjusted in or out on the
motor shaft accordingly.