Manual 2100-670B
Page
8 of 33
To verify or change the wall-mount unit cooling and
heating setpoints in stand alone mode:
1. Connect the TEC-EYE diagnostic tool to the control
board located in the unit.
2. From the Status screen, press UP or DOWN key
until Quick Menu displays Setpoints icon. Press
ENTER key.
3. Press ENTER key to scroll to the selected choice
(see Figure 4).
4. Press UP or DOWN key on desired value until value
displays correctly.
5. Press ENTER key to save and scroll to next
parameter.
6. Press ESCAPE key until Main Menu screen is
displayed.
FIGURE 4
Cool and Heat Setpoints
Information
These screens show unit demand, wall unit status,
serial/model number, hours, run hours, averages and
program version information.
Data (Alarm) Log
The alarm log screens show a log of each alarm. There
will be a log for when alarm occurred and if the alarm
auto clears, it will show when the alarm cleared.
Menu Screens and Password Levels
A
System Config: A1-A10 User
B
Adv Sys Config: B1-B4 Technician
C
I-O Config: C1-C18 Technician
D
On/Off: User
E
Alarm Logs: User
F
Settings
Date/Time: Technician
Language: User
Network Config: Technician
Serial Ports: Technician
Initialization
Clear Logs: User
System Default: Engineer
Restart:
User
Parameter Config: Engineer
Alarm Export: User
G
Logout: Used to log out of the current password
level. Entering back into the menu requires
password.
NOTE:
Screenshots shown in this manual reflect
default settings (when applicable).
User
2000
Technician
1313
Engineer
9254
Use UP or DOWN keys and ENTER key to enter password
TABLE 2
LV1000/TEC-EYE Passwords (Defaults)