Mode
Speed
Percentage
Controller
Output Volts
CFM
Freezestat Active
94.0
9.4 v
1500
High Sensible Full
Load Cooling
94.0
9.4 v
1500
High Sensible Part
Load Cooling
54.0
5.4 v
1100
Standard Full
Load Cooling
63.0
6.3 v
1200
Standard Part
Load Cooling
43.0
4.3 v
950
Economizer Speed
63.0
6.3 v
1200
Heating
63.0
6.3 v
1200
Dehumidification
Mode
19.0
1.9 v
470
TABLE 3A
HR36AP* Blower Speeds
Mode
Speed
Percentage
Controller
Output Volts
CFM
Freezestat Active
80.0
8.0 v
2260
High Sensible Full
Load Cooling
75.0
7.5 v
2180
High Sensible Part
Load Cooling
50.0
5.0 v
1705
Standard Full
Load Cooling
55.0
5.5 v
1830
Standard Part
Load Cooling
35.0
3.5 v
1335
Economizer Speed
45.0
4.5 v
1600
Heating
35.0
3.5 v
1335
Dehumidification
Mode
35.0
3.5 v
1335
TABLE 3B
HR58AP* Blower Speeds
TABLE 4
Rated Airflow
Nominal Rated CFM
Nominal Rated ESP
High
Low
HR36AP*
1200
950
0.00
HR58AP*
1800
1400
0.10
TABLE 5
Indoor Blower Performance
Speed
High
Low
ESP
(Inch H
2
0)
Dry
Coil
Wet
Coil
Dry
Coil
Wet
Coil
HR36AP*
0.00
1260
1200
995
950
HR58AP*
0.10
1885
1800
1470
1400
TABLE 6
Maximum ESP of Operation
Electric Heat Only
* Unit is rated for free blow non-ducted
operation with SGR-5W Supply Grille
and RGR-5W Return Grille.
Model
Static Pressure*
-A0Z
-A05
.00"
.00"
-B0Z
-B06
.00"
.00"
Blower Status Alarm
If the blower is commanded on and the fan status
switch (differential pressure) has not indicated the fan
is running within 45 seconds, the system will generate
an alarm.
This alarm is just a notification and will clear itself
when the conditions are no longer present.
To adjust the air flow alarm delay:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to
System Config
;
press ENTER key.
4. Press UP or DOWN keys to scroll to
Alarm Setup
(A8)
; press ENTER key.
5. Press ENTER key to scroll to
Air Flow Alarm Del
(see Figure 17 on page 16).
6. Press UP or DOWN keys to change to the desired
value.
7. Press ENTER key to save the value.