•  Input the total number of units that will use this 

feature.

•  Set the Lead Unit cooling setpoint.
•  Set the Lead Unit heating setpoint.
•  Set the Lag 1 Unit cooling setpoint.
•  Set the Lag1 Unit heating setpoint.
•  Set the Lag2 Unit cooling setpoint.
•  Set the Lag2 Unit heating setpoint.
•  Set the Lag3 Unit cooling setpoint.
•  Set the Lag3 Unit heating setpoint.

Enable Lead/Lag

Use this option to turn on the lead/lag feature. Press 
ENTER button to enable LEAD/LAG. Press UP or DOWN 
button to change NO to YES. Press ENTER button. 
Default setting is “NO”.

Unit #

Use this option to identify the unit that the ECU Series 
controller will be connected to. For easy identification 
in the future, it is suggested that each wall mount be 
identified with a unit number. This unit number will 
correspond with the controller unit number programmed 
into this setting. Default setting is “1”.

Example:

 Four units are being set up with lead/lag 

operation. Each of the four units are identified 1 thru 
4, and each controller is set up with the corresponding 
unit number 1 thru 4.

Press DOWN button to scroll to Unit #. Press ENTER 
button. Press UP or DOWN button to select unit #. 
Press ENTER button to save unit #.

# of Units

Use this option to identify how many total units will be 
used in lead/lag operation. Default setting is “4”.

Press DOWN button to scroll to # of Units. Press 
ENTER button. Press UP or DOWN button to select # 
of units. Press ENTER button to save # of units. This 
number must be the same on all the units that are used 
in lead/lag operation.

Unit Temperature Setpoints for Cooling and Heating

Cooling and heating setpoints are adjustable for the 
lead unit and up to three lag units. During normal lead/
lag operation, every 24 hours lead operation will rotate 
to the next unit in the unit # order. Lag unit(s) will 
also follow the same unit # rotation. It is important 
that each ECU Series controller has the same value 
for all heating and cooling setpoints to ensure that as 
each unit is selected as Lead, Lag1, Lag2 or Lag3, 
it operates at the same temperature settings. Default 
setpoints are as follows:

•  Lead Unit cooling setpoint is 72°
•  Lead Unit heating setpoint is 70°
•  Lag1 Unit cooling setpoint is 74°
•  Lag1 Unit heating setpoint is 68°
•  Lag2 Unit cooling setpoint is 76°
•  Lag2 Unit heating setpoint is 66°
•  Lag3 Unit cooling setpoint is 78°
•  Lag3 Unit heating setpoint is 64°

Press DOWN button to scroll to LEAD COOL SETPT. 
Press ENTER button. Press UP or DOWN button to 
adjust. Press ENTER button to save.

Repeat above steps for each of the units’ lead and lag 
setpoints as needed.

The Home screen will show the unit lead/lag status 
continually. This is located on the top line of the 
display between the date and time. The screen will 
display one of the following status indicators: LEAD, 
LAG 1, LAG 2, LAG 3. THe lead/lag status determines 
the setpoint that will be used that day. Status will 
rotate based on day of the year.