Manual

2100-559

Page

5 of 6

System Enabling

 (Cont’d.)

Auto

:  Conventional System in “Auto-Changeover” mode.

HVAC system will cycle heating and cooling automatically
to stay within preset heating and cooling Setpoints.

Heating

:  Conventional System in “Heating-Only” mode.

HVAC system will cycle heating in reference to Heating
Setpoint only.  Unit will not activate cooling sequence.

Cooling

:  Conventional System in “Cooling-Only” mode.

Setpoint only.  Unit will not activate heating sequence.
HVAC system will cycle cooling in reference to Cooling

Off:

  HVAC system is inactive.

CCVC

:  “Continuous Compressor, Variable Capacity” application in auto-changeover mode.

HVAC system will cycle heating and cooling automatically to stay within preset heating and
cooling setpoints.  Compressor will modulate from 100% to 20%, but will not shut off.  Typically
used for applications where cycling of compressor is not allowable due to use of on-site generators
– an MRI Mobile Trailer, for instance.

CCFC

:  “Continuous Compressor, Full Capacity” Application in auto-changeover mode.  HVAC

system will cycle heating and cooling automatically to stay within preset heating and cooling
setpoints.  Compressor will not modulate, but will stay at 100% capacity and will not shut off.
Typically, this mode is selected for testing purposes only.

*NOTE

:  Upon initial start-up of any system-enable utilizing compressor, the unit may undergo a series of

self-diagnostics, wherein a series of audible “clicks” are heard.  This may delay compressor function for
up to 5-minutes.

6.

Enter

 button to select chosen operational mode

7.

Left

 button to navigate back to 

Main Menu

 Screen

8.

Left

 button to navigate back to 

Home Page

Temperature Setpoints

 – to access Setpoints from Home Screen, press:

1.

Right

 button to access 

Main Menu 

Screen

2.

Down

 button through entries to highlight 

Setpoints

3.

Enter

 button to select 

Setpoints

 and enter 

Setpoints

 Screen

- Use the 

Up/Down

 buttons to scroll through setpoints

Cool Setpt / Heat Setpt

 are for occupied periods

Cool Setback / Heat Setback

 are for unoccupied periods, and will only be used if scheduling

is enabled (see the 

Advanced Programming

 section)

Min Setpt Diff

 is the closest the Heating and Cooling setpoints can come to one another. (3°F

is recommended minimum)

Deadband

 is the space in degrees from setpoint in which the Cooling and/or Heating sequence

will modulate to 100% capacity (2°F is recommended minimum).

4.

Enter

 button to select specific Setpoint option

5.

Up/Down

 button to enter specific degree amount for setpoint

6.

Enter

 button to save new setpoint.

7.

Left

 button to navigate back to 

Main Menu

 Screen

8.

Left

 button to navigate back to 

Home Page

*

NOTE

:  Although the cooling/heating setpoints can be accessed by simply pressing the arrow keys

during  normal operation, any changes made in this fashion will be for a specific length-of-time as an
“override” feature only.  This temperature change will not be permanent.  See the 

Advanced

Programming

 section for further information.