background image

Manual 2100-760 
Page 

10 of 17

"V" Option CRV Sequence of Operation

The “V” Ventilation option includes a control board with 
blade positioning potentiometers along with an input 
for a 2-10V input signal (see Figure 6).
Adjustable potentiometers:

“PP” Potentiometer setting:

 This potentiometer can be 

used to adjust the blade setting for outdoor air intake 
during a pre-purge cycle. The pre-purge cycle time is 
based on the setting of the pre-purge timer.

“OCC” Potentiometer setting:

 This potentiometer can 

be used to adjust the blade setting for outdoor air 
intake when the “01” terminal is energized on the low 
voltage terminal strip indicating occupancy.

“Y1” Potentiometer setting:

 This potentiometer can be 

used to adjust the blade setting for outdoor air intake 
when the “Y” terminal is energized on the low voltage 
terminal strip indicating 1st stage cooling or Balanced 
Climate operation. When energized, it overrides the 
“OCC” potentiometer setting.

“Y2” Potentiometer setting:

 This potentiometer can be 

used to adjust the blade setting for outdoor air intake 
when the “Y1” terminal is energized on the low voltage 
terminal strip indicating 2nd stage cooling operation. 
When energized, it overrides the “OCC” and “Y1” 
potentiometer settings.

Pre-Purge Feature

Pre-purge is used to ventilate a specified CFM amount 
before occupants enter the room or structure. The 
control board has a built-in pre-purge timer that can 
be set to 30-, 60- and 90-minute intervals by moving 
the jumper noted in Figure 5 on page 9. This timer will 
start when the jumper is installed and the "01" terminal 
is energized on the low voltage terminal strip. Blade 
adjustment can be made on the PP potentiometer. 
Once the timer has timed out, the board will default 
to the occupied setting and this blade position can 
be adjusted on the OCC potentiometer. If the timer is 
set to 0 (off—shipped position), the occupied setting 
is instantaneous and the pre-purge setting (PP) is no 
longer in the sequence.

Occupied Setting

Occupied is used to ventilate a specified CFM amount 
when occupants enter the room or structure. The 
control board will energize the occupied setting 
after the pre-purge cycle, or if pre-purge is disabled 
immediately when the "01" terminal is energized on the 
low voltage strip. Blade adjustment can be made on the 
OCC potentiometer.

Y1 Setting

Y1 is used to ventilate a specified CFM amount when 
Y cooling is energized. The control board will energize 
the Y1 setting when Y is energized on the low voltage 
strip. Blade adjustment can be made on the Y1 

90
60
30

0

FIGURE 6

CRV Control Board

potentiometer. This potentiometer setting overrides the 
OCC occupied setting.

Y2 Setting

Y2 is used to ventilate a specified CFM amount when 
Y1 cooling is energized. The control board will energize 
the Y2 setting when Y1 is energized on the low voltage 
strip. Blade adjustment can be made on the Y2 
potentiometer. This potentiometer setting overrides the 
OCC occupied and the Y1 setting.

2-10V Operation

A CO

2

 sensor or other device sending a 2-10V signal 

can be used to control the damper motor. Two control 
methods are available to control the damper motor:
•  Method 1: The control board will accept a 

2-10VDC signal with a resistive load greater than 
5000 ohms. Bard CO

2

 sensor 8403-096 can be 

used when the 2-10V output is connected to the 
blade connector on the unlanded gray wire from 
the CRV, located near the unit low voltage terminal 
strip. The occupied OCC potentiometer setting 
must be set to the off position for total modulation. 
The OCC potentiometer can be used to maintain a 
minimum blade position when "01" is energized.

•  Method 2: The damper motor will accept a 

2-10VDC signal with a resistive load less than 
5000 ohms. This method involves bypassing the 
control board and powering the motor directly from 
the device providing the 2-10VDC modulating 
signal. The gray wire connected to CO

2

 VIN on the 

control board must be spliced with the white wire 

Summary of Contents for CRVS-5A

Page 1: ...rd Heat Pump Models T36 60H and T36 60S Commercial Room Ventilator with Exhaust Model CRVS 5A INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 760...

Page 2: ...Left Hand CRVS 5A Units Only 6 Figure 4 Install Ventilator 7 Figure 5 CRV Control Board 9 Figure 6 CRV Control Board 10 Figure 7 8403 096 CO2 Sensor Set Up 12 Figure 8 CRV Control Board Wiring 13 Figu...

Page 3: ...in exhaust provisions When the damper blade opens to bring fresh air in the damper also opens an exhaust relief The exhaust air will flow into the condenser section of the unit The condenser fan will...

Page 4: ...ventilator with attached electrical harness and miscellaneous hardware 2 Remove and save the existing exterior blower access and service access panels on the Bard wall mount unit see Figure 1 FIGURE...

Page 5: ...0 760 Page 5 of 17 3 Remove and save existing unit air filter and screws from front center grille see Figure 2 FIGURE 2 Removal of Air Filter and Exhaust Cover Plate 4 Remove and discard the exhaust c...

Page 6: ...GURE 3 Reroute Wires for Left Hand CRVS 5A Units Only 6 Insert ventilator into the unit to the far left side clearing the right filter bracket see Figure 4 Once the ventilator is fully inserted slide...

Page 7: ...assembly Note When installing CRV position so hole in front Plug the 4 125 holes in the service door with insert a self drilling screw WIRES in condenser grille to lip is centered over hole CRV in un...

Page 8: ...nt for Desired Ventilator Air The amount of ventilation air supplied by the commercial room ventilator is dependent on four 4 factors 1 Return air duct static pressure drop 2 Supply air duct static pr...

Page 9: ...E COOLING POT Y1 SETTING FOR WHEN Y2 IS ENERGIZED COOLING OR BLADE POSITION Y1 WILL OVERRIDE OCC POT PP PRE PURGE SET FOR PREOCCUPANCY POT OCC OCCUPIED SETTING TURN OFF FOR C02 FULL MODULATION SETTING...

Page 10: ...ccupied setting is instantaneous and the pre purge setting PP is no longer in the sequence Occupied Setting Occupied is used to ventilate a specified CFM amount when occupants enter the room or struct...

Page 11: ...other end of the gray wire should be connected to the CO2 sensor as stated in Method 1 During 2 10VDC operation with 01 energized and pre purge timed operation active DC voltage signaling occupancy f...

Page 12: ...TO CHANGE ANY SETTINGS WITH THE SIDE BUTTONS TO LOCK THE CO2 DIP SWITCHES MUST BE POSITIONED AS SHOWN FOR PROPER OPERATION MIS 4025 C Settings Recommended Default RON RELAY ON SET POINT 725 ROF RELAY...

Page 13: ...LE STAGE UNIT D FIELD JUMPER FOR CONSTANT VENTILATION BLACK WHITE BROWN WHITE ORANGE BROWN WHITE RELAY BLACK WHITE 56 30 0 CRV CONTROL BOARD 60 Damper Motor RED BLACK BROWN A CO2 Sensor 90 A OPTIONAL...

Page 14: ...Heating Mode Total Air Cooling Heating Mode 0 200 400 600 800 1000 1200 1400 A B C D E F Airflow CFM Blade Position T42S1 with CRVS 5 CRVP 5 CHCRV 5 Vent Air Cooling Heating Mode Total Air Cooling Hea...

Page 15: ...h Speed Comp Vent Airflow0 2 ESP A B C D E F 0 100 200 300 400 500 600 700 0 2 4 6 8 10 12 14 16 18 Air flow CFM VentPosition T60S1VentAirflow High SpeedComp Vent Airflow 0 2 ESP Blower Only Vent Airf...

Page 16: ...Manual 2100 760 Page 16 of 17 MIS 347A Supply Air Evaporator Coil DAMPER BLADE EXHAUST AIR Return Air Condenser Air Direction Condenser Coil Outside Air FIGURE 9 Call for Blower Operation...

Page 17: ...Manual 2100 760 Page 17 of 17 FIGURE 10 Call for Compressor or Fan Only with Ventilation Off MIS 348A Supply Air Return Air Evaporator Coil DAMPER BLADE Condenser Air Direction Condenser Coil...

Reviews: