Bard CRVS-5A Installation Instructions Manual Download Page 3

Manual 2100-760 
Page 

3 of 17

General Information

The ventilator should only be installed by a trained 
heating and air conditioning technician. These 
instructions serve as a guide to the technician 
installing the ventilator package. They are not 
intended as a step-by-step procedure with which the 
mechanically inclined owner can install the package.
The ventilator housing is shipped in one carton which 
contains the electrical harness, miscellaneous hardware 
and installation instructions.

Unpacking

Upon receipt of the equipment, be sure to compare the 
model number found on the shipping label with the 
accessory identification information on the ordering and 
shipping document to verify that the correct accessory 
has been shipped.
Inspect the carton housing of each ventilator as it is 
received. Before signing the freight bill, verify that all 
items have been received and that there is no visible 
damage. Note any shortages or damage on all copies 
of the freight bill. The receiving party must contact 
the last carrier immediately, preferably in writing, 
requesting inspection by the carrier’s agent. Concealed 
damage not discovered until after loading must be 
reported to the carrier within 15 days of its receipt.

Description

The CRVS-5A ventilator is designed to be used with 
Bard heat pump models T36-60H and T36-60S. It is 
an electromechanical vent system designed to provide 
fresh air to meet indoor air quality standards.

Models

When installed in the above listed models, the CRV 
provides built-in exhaust provisions. When the damper 
blade opens to bring fresh air in, the damper also 
opens an exhaust relief. The exhaust air will flow into 
the condenser section of the unit. The condenser fan 
will help draw exhaust air out.

CRV Features

•  One piece construction—easy to install with no 

mechanical linkage adjustment required.

•  Exhaust air damper—built in with positive closed 

position. Provides exhaust air capability to prevent 
pressurization of tight buildings.

•  Actuator motor—24 volt, power open, spring return 

with built-in torque limiting switch.

•  Provides up to 75% of outside air.

GENERAL 

Electrical shock hazard.

Disconnect remote electrical power supply 
or supplies before servicing.

Failure to do so could result in electric 
shock or death.

!

WARNING

Exposed moving parts.

Disconnect all electrical power before 
servicing.

Failure to do so can result in severe injury 
or amputation.

!

WARNING

Sharp metallic edges.

Take care and wear appropriate protective 
devices to avoid accidental contact with 
sharp edges.

Failure to do so can result in personal injury.

!

CAUTION

Sequence of Operation

On a call for blower operation, CRV will open to 
pre-purge position as set by "PP" potentiometer 
for the amount of time set by the PP jumper. The 
CRV will then move to the position set by the "OCC" 
potentiometer. If PP jumper is in 0 position, the CRV 
will immediately open to the position set by the "OCC" 
potentiometer.
A call for 1st stage cooling or heating cycles the 
compressor, and the dampers reposition to the 
Y1potentiometer setpoint. A call for 2nd stage 
cooling or heating energizes compressor solenoid and 
repositions the damper blade to the Y1 potentiometer 
position. On loss of blower operation, CRV closes fully.

Summary of Contents for CRVS-5A

Page 1: ...rd Heat Pump Models T36 60H and T36 60S Commercial Room Ventilator with Exhaust Model CRVS 5A INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 760...

Page 2: ...Left Hand CRVS 5A Units Only 6 Figure 4 Install Ventilator 7 Figure 5 CRV Control Board 9 Figure 6 CRV Control Board 10 Figure 7 8403 096 CO2 Sensor Set Up 12 Figure 8 CRV Control Board Wiring 13 Figu...

Page 3: ...in exhaust provisions When the damper blade opens to bring fresh air in the damper also opens an exhaust relief The exhaust air will flow into the condenser section of the unit The condenser fan will...

Page 4: ...ventilator with attached electrical harness and miscellaneous hardware 2 Remove and save the existing exterior blower access and service access panels on the Bard wall mount unit see Figure 1 FIGURE...

Page 5: ...0 760 Page 5 of 17 3 Remove and save existing unit air filter and screws from front center grille see Figure 2 FIGURE 2 Removal of Air Filter and Exhaust Cover Plate 4 Remove and discard the exhaust c...

Page 6: ...GURE 3 Reroute Wires for Left Hand CRVS 5A Units Only 6 Insert ventilator into the unit to the far left side clearing the right filter bracket see Figure 4 Once the ventilator is fully inserted slide...

Page 7: ...assembly Note When installing CRV position so hole in front Plug the 4 125 holes in the service door with insert a self drilling screw WIRES in condenser grille to lip is centered over hole CRV in un...

Page 8: ...nt for Desired Ventilator Air The amount of ventilation air supplied by the commercial room ventilator is dependent on four 4 factors 1 Return air duct static pressure drop 2 Supply air duct static pr...

Page 9: ...E COOLING POT Y1 SETTING FOR WHEN Y2 IS ENERGIZED COOLING OR BLADE POSITION Y1 WILL OVERRIDE OCC POT PP PRE PURGE SET FOR PREOCCUPANCY POT OCC OCCUPIED SETTING TURN OFF FOR C02 FULL MODULATION SETTING...

Page 10: ...ccupied setting is instantaneous and the pre purge setting PP is no longer in the sequence Occupied Setting Occupied is used to ventilate a specified CFM amount when occupants enter the room or struct...

Page 11: ...other end of the gray wire should be connected to the CO2 sensor as stated in Method 1 During 2 10VDC operation with 01 energized and pre purge timed operation active DC voltage signaling occupancy f...

Page 12: ...TO CHANGE ANY SETTINGS WITH THE SIDE BUTTONS TO LOCK THE CO2 DIP SWITCHES MUST BE POSITIONED AS SHOWN FOR PROPER OPERATION MIS 4025 C Settings Recommended Default RON RELAY ON SET POINT 725 ROF RELAY...

Page 13: ...LE STAGE UNIT D FIELD JUMPER FOR CONSTANT VENTILATION BLACK WHITE BROWN WHITE ORANGE BROWN WHITE RELAY BLACK WHITE 56 30 0 CRV CONTROL BOARD 60 Damper Motor RED BLACK BROWN A CO2 Sensor 90 A OPTIONAL...

Page 14: ...Heating Mode Total Air Cooling Heating Mode 0 200 400 600 800 1000 1200 1400 A B C D E F Airflow CFM Blade Position T42S1 with CRVS 5 CRVP 5 CHCRV 5 Vent Air Cooling Heating Mode Total Air Cooling Hea...

Page 15: ...h Speed Comp Vent Airflow0 2 ESP A B C D E F 0 100 200 300 400 500 600 700 0 2 4 6 8 10 12 14 16 18 Air flow CFM VentPosition T60S1VentAirflow High SpeedComp Vent Airflow 0 2 ESP Blower Only Vent Airf...

Page 16: ...Manual 2100 760 Page 16 of 17 MIS 347A Supply Air Evaporator Coil DAMPER BLADE EXHAUST AIR Return Air Condenser Air Direction Condenser Coil Outside Air FIGURE 9 Call for Blower Operation...

Page 17: ...Manual 2100 760 Page 17 of 17 FIGURE 10 Call for Compressor or Fan Only with Ventilation Off MIS 348A Supply Air Return Air Evaporator Coil DAMPER BLADE Condenser Air Direction Condenser Coil...

Reviews: