Manual 7960-847B
Page 

3 of 8

FIGURE 2

MIS-3880

REINSTALL CAP

REMOVE CAP AND INSTALL

PRESSURE TRANSDUCER

TEE TO SERVICE PORT.

BOX

PLUG WITH

WIRES TO CONTROL 

LIQUID LINE

RE-INSTALL CAP

page 6. Disconnect the black fan wire running 
from the T2 terminal of the compressor contactor. 
Install terminal block (as shown in Figure 5) and 
reconnect the black fan wire to one side of the 
terminal block. Run the black/red wire from LAC 
to the terminal block so that it is connected to the 
fan motor wire. Run the black wire from LAC to the 
T2 terminal of the compressor contactor. Run the 
black/white wire from LAC to the C terminal on the 
24V transformer. Run the red/white wire from LAC 
to the R (hot) terminal on the transformer. Run 
the yellow wire from LAC to the T3 terminal of the 
compressor contactor.

8.  Secure wires running on the outdoor section of the 

unit using the supplied nylon wire ties as shown 
in Figure 1). Be sure that there is no way that the 
wires can come in contact with the fan blades or 
any sharp edges.

9.  Check wiring and control knob settings. See Figure 

5 (page 6) and Figure 6 (page 7) for wiring and 
suggested setpoints.

10. Find the purple wire not connected to anything that 

is tucked in the cable duct (see Figure 5). Pull it 

out and connect it to the LAC terminal block on 
the terminal that is separate from the LAC control 
wires. Connect the end of the outdoor temperature 
switch that has the insulated quick connect to the 
terminal block beside the purple wire. Connect the 
other end of the outdoor temperature switch to the 
Y terminal on the phase monitor. (Refer to Figure 7 
on page 8 or the unit wiring diagram).

11. Connect the freeze protect thermostat wires in line 

with the “Y” input signal to the compressor control 
module (CCM). Refer to the unit wiring diagram.

 

For 1-phase units, connect the end with the 1/4” 
quick connect to Y terminal on the CCM, and the 
other end with the 1/4” tab to the yellow/white wire 
coming from the low voltage terminal strip. 

 

For 3-phase units, connect the wire end with 
the 1/4” quick connect to “Y out” on the phase 
monitor, and the other end with the 1/4” tab to the 
yellow/black wire going to the CCM.

12. Apply “This unit is equipped with CMA-38 control 

module” label to the inside of the inner control 
panel cover above the wiring diagrams.

11/16" WRENCH

3/4" WRENCH

1/2" WRENCH

Summary of Contents for CMA-38

Page 1: ...lon Wire Ties 6 7961 312 0338 CMA 38 Unit I D Label Field supplied tools needed Personal protection equipment including gloves and safety glasses 5 16 nut driver 1 2 wrench service port 11 16 wrench L...

Page 2: ...peed control box to the pressure switch as shown in Figure 2 5 Install outdoor temperature switch assembly to the fan shroud and route wires through the bushing and up to the control panel as shown in...

Page 3: ...e Figure 5 page 6 and Figure 6 page 7 for wiring and suggested setpoints 10 Find the purple wire not connected to anything that is tucked in the cable duct see Figure 5 Pull it out and connect it to t...

Page 4: ...Sequence of Operation Upon initiation the CMA 38 will apply full voltage to the fan motor for the time period selected with the Hard Start knob see Figure 6 Hard start time is adjustable from 0 1 to 5...

Page 5: ...E ONE OF THE MIDDLE HEADER STUBS TO ATTACH THE FREEZE STAT TO THE EVAPORATOR COIL FREEZE STAT WIRES RUN DOWN COPPER THROUGH THE GROMMET AND INTO THE CONTROL PANEL WITH THE BLOWER MOTOR WIRES Manual 79...

Page 6: ...FIGURE 5 MIS 4074 MOTOR FROM FAN MODULATING LOW AMBIENT BOX MIS 4074 TRANSFORMER COMPRESSOR CONTACTOR TERMINAL BLOCK CABLE DUCT Manual 7960 847B Page 6 of 8...

Page 7: ...881 A Black Red Yellow Black top 2 pins N O Setting position Set to MIN position Set to MIN position Set to 315 RED BLACK BLACK WHITE BLUE Set jumper to TO PRESSURE TRANSDUCER RED WHITE Manual 7960 84...

Page 8: ...Behind Low Voltage Block 12 Pin Plug Blue on UNITS 3 PHASE Low Ambient W24 Units MONITOR Outdoor Contactor Compressor Terminal Block 2 Control Module Compressor Brown on Black Black Yellow Yellow UNI...

Reviews: