background image

Manual 2100-586G 

Page 

16 of 25

Defrost Cycle

The defrost cycle is controlled by temperature and time 
on the solid state heat pump control.
When the outdoor temperature is in the lower 
40°F temperature range or colder, the outdoor coil 
temperature is 32°F or below. This coil temperature is 
sensed by the coil temperature sensor mounted near 
the bottom of the outdoor coil. Once coil temperature 
reaches 30°F or below, the coil temperature sensor 
sends a signal to the control logic of the heat pump 
control and the defrost timer will start accumulating 
run time.
After 30, 60 or 90 minutes of heat pump operation at 
30°F or below, the heat pump control will place the 
system in the defrost mode.
During the defrost mode, the refrigerant cycle switches 
back to the cooling cycle, the outdoor motor stops, 
electric heaters are energized and hot gas passing 
through the outdoor coil melts any accumulated frost.  
When the temperature rises to approximately 57°F, the 
coil temperature sensor will send a signal to the heat 
pump control which will return the system to heating 
operations automatically.
If some abnormal or temporary condition such as a high 
wind causes the heat pump to have a prolonged defrost 
cycle, the heat pump control will restore the system to 
heating operation automatically after 8 minutes.
The heat pump defrost control board has an option of 
30-, 60- or 90-minute setting. By default, this unit 
is shipped from the factory with the defrost time on 
the 60-minute pin. If circumstances require a change 
to another time, remove the wire from the 60-minute 
terminal and reconnect to the desired terminal (see 
Figure 8).
There is a cycle speed up jumper on the control. This 
can be used for testing purposes to reduce the time 
between defrost cycle operation without waiting for 
time to elapse.
Use a small screwdriver or other metallic object, 
or another ¼" QC, to short between the 

SPEEDUP 

terminals to accelerate the HPC timer and initiate 
defrost.
Be careful not to touch any other terminals with the 
instrument used to short the 

SPEEDUP

 terminals. 

It may take up to 10 seconds with the 

SPEEDUP

 

terminals shorted for the speedup to be completed and 
the defrost cycle to start.

As soon as the defrost cycle kicks in, remove the 

shorting instrument from the SPEEDUP terminals.

 

Otherwise the timing will remain accelerated and 
run through the 1-minute minimum defrost length 
sequence in a matter of seconds and will automatically 
terminate the defrost sequence.

There is an initiate defrost jumper (sen jump) on the 
control that can be used at any outdoor ambient during 
the heating cycle to simulate a 0° coil temperature.
This can be used to check defrost operation of the unit 
without waiting for the outdoor ambient to fall into the 
defrost region.
By placing a jumper across the 

SEN JMP

 terminals 

(a ¼" QC terminal works best), the defrost sensor 
mounted on the outdoor coil is shunted out and will 
activate the timing circuit. This permits the defrost 
cycle to be checked out in warmer weather conditions 
without the outdoor temperature having to fall into the 
defrost region.
In order to terminate the defrost test, the 

SEN JMP

 

jumper must be removed. If left in place too long, the 
compressor could stop due to the high pressure control 
opening because of high pressure condition created 
by operating in the cooling mode with outdoor fan off. 
Pressure will rise fairly fast as there is likely no actual 
frost on the outdoor coil in this artificial test condition.
There is also a 5-minute compressor time delay function 
built into the HPC. This is to protect the compressor 
from short cycling conditions. The board’s LED will have 
a fast blink rate when in the compressor time delay. In 
some instances, it is helpful to the service technician to 
override or speed up this timing period and shorting out 
the 

SPEEDUP

 terminals for a few seconds can do this.

Low Pressure Switch Bypass Operation

 – The control has 

a selectable (SW1) low pressure switch bypass set up to 
ignore the low pressure switch input during the first (30, 
60, 120 or 180 seconds) of “Y” operation.
After this period expires, the control will then monitor the 
low pressure switch input normally to make sure that the 
switch is closed during “Y” operation.

High Pressure Switch Operation

 – The control has a 

built-in lockout system that allows the unit to have the 
high pressure switch trip up to two times in 1 hour and 
only encounter a “soft” lockout. A “soft” lockout shuts 
the compressor off and waits for the pressure switch to 
reset, which at that point then allows the compressor to 
be restarted as long as the 5-minute short cycle timer 
has run out. If the high pressure switch trips a third time 
within 1 hour, the unit is in “hard” lockout indicating 
something is certainly wrong and it will not restart itself.

Summary of Contents for C36H1-A

Page 1: ...Models INSTALLATION INSTRUCTIONS C36H1 A C36H1 B C36H1 C C42H1 A C42H1 B C42H1 C C48H1 A C48H1 B C48H1 C C60H1 A C60H1 B C60H1 C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual...

Page 2: ...e Sensor Outside Unit Circuit 19 Fan Blade Setting Dimensions 20 Removal of Fan Shroud 20 R 410A Refrigerant Charge 20 Troubleshooting ECM Indoor Blower Motors 24 FIGURES Figure 1 Fresh Air Damper Ass...

Page 3: ...OPTIONS X Beige 1 White 4 Buckeye Gray 5 Desert Brown 8 Dark Bronze S Stainless Steel CAPACITY 36 3 Ton 42 3 Ton 48 4 Ton 60 5 Ton VENTILATION OPTIONS B Blank off Plate V Commercial Ventilator Mod Sp...

Page 4: ...led in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type NFPA No 90A and Residence...

Page 5: ...ersonal injury The safety alert symbol shall not be used with this signal word As an alternative to NOTICE the word CAUTION without the safety alert symbol may be used to indicate a message not relate...

Page 6: ...s used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm NOTE If no return air duct...

Page 7: ...tible wall Placement 1 On side by side installations maintain a minimum of 20 clearance on right side to allow access to control panel and heat strips and to allow proper airflow to the outdoor coil A...

Page 8: ...ket optional use for direct mount not used when unit installed with curb C H RIGHT UNIT FIGURE 2 All dimensions are in inches Dimensional drawings are not to scale Dimensions of Basic Unit for Archite...

Page 9: ...LY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME O...

Page 10: ...PPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1 4 INCH CLEARANCE TO COMBUSTIBLE SURFACES Fire hazard Maintain minimum 1 4 clearance between the supply air duct and combustible materials in the first 3 o...

Page 11: ...IR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Page 12: ...best unit performance and efficiency Review duct grille or return duct work Avoid using restrictive duct work to Unit Mount Return Grille Fixed Blade Wall wall Outside Wall Ducted Installations Adjus...

Page 13: ...anel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing entry See Start Up section for important information on t...

Page 14: ...come out of the charging cylinder tank as a liquid to avoid any fractionation and to ensure optimal system performance Refer to instructions for the cylinder that is being utilized for proper method...

Page 15: ...leaning of the outdoor coil to permit full and unrestricted airflow circulation is essential Sequence of Operation Cooling Stage 1 Circuit R Y makes at thermostat pulling in compressor contactor start...

Page 16: ...wise the timing will remain accelerated and run through the 1 minute minimum defrost length sequence in a matter of seconds and will automatically terminate the defrost sequence There is an initiate d...

Page 17: ...25 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 MIS 2668 A OFF LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED DEFROST TIME TIMER FACTORY SETTING 60 MIN ON FIG...

Page 18: ...rmer is bad or the unit wiring is incorrect 10 Check for Compressor output signal Is there 24 volts AC between CC C Yes go to Step 12 No go to Step 13 11 No Y compressor input signal Check thermostat...

Page 19: ...6 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757...

Page 20: ...ty The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information should only be used by certified tec...

Page 21: ...WB LOW SIDE HIGH SIDE 147 321 147 341 147 362 148 387 150 415 151 444 153 476 156 510 158 548 161 587 C48H 75 DB 62 WB LOW SIDE HIGH SIDE 137 315 137 336 138 360 139 385 141 412 142 442 143 473 145 50...

Page 22: ...3 8 45 52 50 60 8 6 10 10 A20 1 or 3 113 125 2 6 45 52 52 50 60 52 8 6 6 10 10 10 C60H1 B0Z 230 208 60 3 1 32 45 8 10 B06 1 50 60 8 10 B09 1 59 60 6 10 B15 1 59 60 6 10 B18 2 N A N A N A N A 59 28 60...

Page 23: ...variable speed ECM indoor motor that automatically adjusts itself to maintain approximately the same rate of indoor airflow in both heating cooling dry and wet coil conditions and at both 230 208 or 4...

Page 24: ...ontrol replacement check Perform Moisture Check Motor won t start Motor rocks but won t start Check for loose or compliant motor mount Make sure blower wheel is tight on shaft Perform motor control re...

Page 25: ...motor plug just removed to the motor shell is 100K ohms see Figure 11 Measure to unpainted motor end plate If any motor lead fails this test do not proceed to install the control module the motor is d...

Reviews: