background image

Manual 2100-586D 

Page 

18 of 25

Symptom

Description, Check & Possible Causes

What & How to Check / Repair 

Compressor will 

not start (heating 

or cooling)

1.  Check for LED illumination.

Is there an LED illuminated on the board (flashing)?

Yes = go to Step #2; No = go to Step #

2.  Check for error codes.

Is the LED flashing a Code?

Yes = go to Step #4; No = go to Step #8

3.  Check for power at board.

Is there 24 volts AC between R and C?

Yes = go to Step #13; No = go to Step #9

4.  Check codes.

What code is blinking?

Code "1", go to Step #6; Code "2", go to Step#7; Fast Blink, go to Step #5

5.  Compressor delay active.

Wait for 5 minute delay or jump board's "speed up pins".

Check for proper operation; if still needed, go back to Step #1.

6.  Low pressure fault.

Check wiring circuit and unit pressures.

7.  High pressure fault.

Check wiring circuit and unit pressures.

8.  Check for Compressor input signal.

Is there 24 volts AC between Y and C?

Yes = go to Step #10; No = go to Step #11

9.  No power to board.

The unit either does not have unit voltage, the transformer is bad or the unit 

wiring is incorrect.

10.  Check for Compressor output signal.

Is there 24 volts AC between CC & C?

Yes = go to Step #12; No = go to Step #13

11.  No "Y" compressor input signal.

Check thermostat wiring, incorrect phase of unit (see section on Phase Monitor), 

and finally unit wiring.

12.  No "CC" compressor output signal.

Check compressor contactor for proper operation and finally check compressor.

13.  Faulty board.

Replace defrost board.

Fan outdoor motor 

does not run  

(cooling or heating 

except during 

defrost)

Heat pump control defective

Check across fan relay on heat pump control. (Com-NC)

Replace heat pump control.

Motor defective

Check for open or shorted motor winding.  Replace motor.

Motor capacitor defective

Check capacitor rating.  Check for open or shorted capacitor.  Replace capacitor.

Reversing valve 

does not energize

(heating only)

Heat pump control defective

Check for 24V between RV-C and B-C.

1. Check control circuit wiring.

2. Replace heat pump control.

Reversing valve solenoid coil defective

Check for open or shorted coil.

Replace solenoid coil.

Unit will not go 

into defrost

(heating only)

Temperature sensor or heat pump control defective

Disconnect temperature sensor from board and jumper across "SPEEDUP" 

terminals and "SEN JMP" terminals.  This should cause the unit to go through a 

defrost cycle within one minute.

1. If unit goes through defrost cycle, replace temperature sensor.

2. If unit does not go through defrost cycle, replace heat pump control.

Unit will not come 

out of defrost

(heating only)

Temperature sensor or heat pump control defective

Jumper across "SPEEDUP" terminal.

This should cause the unit to come out of defrost within one minute. 

1. If unit comes out of defrost cycle, replace temperature sensor.

2. If unit does not come out of defrost cycle, replace heat pump control.

TROUBLESHOOTING

TABLE  3   TROUBLESHOOTING

SOLID STATE HEAT PUMP CONTROL 

TROUBLESHOOTING PROCEDURE

 1. 

NOTE:

 

A thorough understanding of the defrost  

    cycle sequence is essential.  Review that section  

    earlier in this manual prior to troubleshooting the  

    control.  

Turn on AC power supply to unit.

  2.  Turn thermostat blower switch to “fan on” – the  

    indoor blower should start.  (If it doesn’t,  

 

    troubleshoot indoor unit and correct problem.)
  3.  Turn thermostat blower to “auto” position.  Indoor  

    blower should stop.  

NOTE:

 

Many models have a  

    1-minute blower time delay on “off” command;  

    wait for this to time-out.

  4.  Set system switch to “heat” or “cool”.  Adjust    

    thermostat to call for heat or cool.  The indoor    

    blower, compressor and outdoor fan should start.

NOTE:  If there was no power to 24 volt transformer,    

 

the compressor and outdoor fan motor will    

 

not start for 5 minutes.  This is because of  

 

 

the compressor short cycle protection. 

LED BLINK CODES

  BLINK 

FUNCTION

  Slow 

Normal function (1.0 sec on/1.0 sec off)

  Fast 

ASCD (Compressor Delay) timer active  

   

(0.1 sec on/0.1 sec off)

  1 

Low pressure switch failure

  2 

High pressure switch failure/“Soft” Lockout

  3 

Defrost mode active

  4 

High pressure switch failure/“Hard” Lockout

Summary of Contents for C24H1-A

Page 1: ...INSTRUCTIONS C24H1 A C24H1 B C30H1 A C30H1 B C30H1 C C36H1 A C36H1 B C36H1 C C42H1 A C42H1 B C42H1 C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 586D Supersedes 2100 5...

Page 2: ...C H 22 Table 7 Indoor Blower Performance 23 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Filters...

Page 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Page 4: ...o methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Cond...

Page 5: ...t is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm NOTE If no return air du...

Page 6: ...ers on the lag bolts 7 Secure rain flashing to wall and caulk across entire length of top See Figures 3A 3B 8 For additional mounting rigidity the return air and supply air frames or collars can be dr...

Page 7: ...ns of Basic Unit for Architectural Installation Requirements Nominal MODEL WIDTH W DEPTH D HEIGHT H SUPPLY RETURN A B C B E F G I J K L M N O P Q R S T C24H1 C30H1 38 200 17 125 70 563 7 88 27 88 13 8...

Page 8: ...LEARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CAU...

Page 9: ...TURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHIN...

Page 10: ...This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible...

Page 11: ...IR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Page 12: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 13: ...ccess panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing entry See Start Up section for important informati...

Page 14: ...tiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Page 15: ...However reverse operation for over one hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rotation for several minutes the compressor s...

Page 16: ...heat pump defrost control board has an option of 30 60 or 90 minute setting By default this unit is shipped from the factory with the defrost time on the 60 minute pin If circumstances require a chang...

Page 17: ...25 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 MIS 2668 A OFF LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED DEFROST TIME TIMER FACTORY SETTING 60 MIN ON FIG...

Page 18: ...RV C and B C 1 Check control circuit wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replace solenoid coil Unit will not go into defrost heat...

Page 19: ...8 36 29157 74 10762 112 4464 1 88139 37 28355 75 10501 113 4367 0 85371 38 27577 76 10247 114 4274 1 82699 39 26823 77 10000 115 4182 2 80121 40 26092 78 9760 116 4093 3 77632 41 25383 79 9526 117 400...

Page 20: ...th this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information sho...

Page 21: ...GH SIDE 133 302 133 321 133 341 134 365 136 391 137 418 138 449 141 481 143 516 146 553 80 DB 67 WB LOW SIDE HIGH SIDE 142 310 142 329 142 350 143 374 145 401 146 429 148 460 151 493 153 529 156 567 8...

Page 22: ...60 1 1 22 30 10 10 A04 1 42 50 8 10 AS8 1 48 50 8 10 AF8 1 or 2 63 70 6 8 22 42 30 45 10 8 10 10 C24H1 B0Z 230 208 60 3 1 15 20 12 12 B06 1 33 35 8 10 B09 1 42 45 8 10 C30H1 A0Z 230 208 60 1 1 23 30...

Page 23: ...hese units are equipped with a variable speed ECM indoor motor that automatically adjusts itself to maintain approximately the same rate of indoor airflow in both heating cooling dry wet coil conditio...

Page 24: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Page 25: ...is correct for your application Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 w...

Reviews: