2. Installation requirements
2.2
Electrical requirements
Power requirements
One TF-10 tile requires 200-240 VAC, 50-60 Hz, 1.98 amps at 230 VAC. Each TF-10 tile has a power loop through connector.
However, MAXIMUM 6 TF-10 tiles may be connected in parallel. So, one power source cable has to be provided per 6 tiles. Every
power source cable should be protected by a circuit breaker or fuses rated 16 A / 250 VAC (15 A / 250 VAC in the USA and Canada).
Barco provides a range of power boxes, which meet the requirements of your
fi
xed TF-10 display. Contact
Barco for more information about power boxes and power requirements for your
fi
xed TF-10 display.
Power system:
It is recommended to use a TN-S power distribution system (a power distribution system with a separate neutral and grounding
conductor) in order to avoid large ground current loops due to voltage differences in the neutral conductor. The total electrical
installation should be protected by an appropriately rated disconnect switch, circuit breakers, over voltage protector and Ground Fault
Current Interrupters. The installation shall be done according to the local electrical installation codes. In Europe special attention
should be given to EN 60364, the standard for electrical installation of buildings. In Germany VDE 0100 should be adhered to. In
America, special attention should be given to the National Electrical Code, ANSI/NFPA 70.
Disconnect device:
When the appliance inlets of the individual tiles are not accessible, the socket outlets supplying the rack shall be installed near the
equipment and be easily accessible, or a readily accessible general disconnect device shall be incorporated in the
fi
xed wiring.
This equipment MUST be earthed:
In order to protect against risk of electric shock, the installation should be properly grounded. Defeating the purpose of the grounding
type plug will expose you to the risk of electric shock.
R59770682 FIXED TF-10 DISPLAY 23/11/2011
11
Summary of Contents for TF-10
Page 1: ...Fixed TF 10 display Installation Manual R59770682 02 23 11 2011 ...
Page 4: ......
Page 6: ...Table of contents 2 R59770682 FIXED TF 10 DISPLAY 23 11 2011 ...
Page 12: ...1 Safety 8 R59770682 FIXED TF 10 DISPLAY 23 11 2011 ...
Page 30: ...3 Components of a fixed TF 10 display 26 R59770682 FIXED TF 10 DISPLAY 23 11 2011 ...
Page 40: ...4 Physical installation 36 R59770682 FIXED TF 10 DISPLAY 23 11 2011 ...
Page 46: ...5 Cabling of an TF 10 display 42 R59770682 FIXED TF 10 DISPLAY 23 11 2011 ...
Page 56: ...7 Specifications 52 R59770682 FIXED TF 10 DISPLAY 23 11 2011 ...