2. Custom Power Box
Article No.
Description
R9851253
Custom Power Box 3 phase 400VAC — 5 multi-pole output connectors and 1 auxiliary outlet.
R9851254
Custom Power Box 3 phase 400VAC — 6 multi-pole output connectors and 1 auxiliary outlet.
R9851255
Custom Power Box 3 phase 400VAC — 7 multi-pole output connectors and 1 auxiliary outlet.
R9851256
Custom Power Box 3 phase 400VAC — 8 multi-pole output connectors and 1 auxiliary outlet.
R9851257
Custom Power Box 3 phase 400VAC — 9 multi-pole output connectors and 1 auxiliary outlet.
R9851258
Custom Power Box 3 phase 400VAC — 10 multi-pole output connectors and 1 auxiliary outlet.
2.3 Technical summary
Summary:
Type
Value
Main circuit breaker
3 phase plus neutral (N)
Power boxes with less then four multi pole output connectors are provided with
a ground fault current interrupter of 300 mA. Power boxes with four or more
multi pole output connectors are provided with a ground fault current interrupter
adjustable between 30 mA and 10 mA.
Multi-pole output connectors
19 pins circular multi-pole connectors with each 6 circuits. Each circuit is protected
with a 16 A switch fuse (20 kA short circuit rating).
Auxiliary connector
2 phase, plus protective earth, auxiliary connectors (CEE-form) protected with a 16
A switch fuse (20 kA short circuit rating).
Input voltage
230VAC 3 phase plus neutral or 400VAC 3 phase plus neutral.
Suitable power nets
TT, TN-S and TN-C power distribution systems. Do not use this power box on an
IT power distribution system.
Output voltage
230V on each output circuit (multi-pole and auxiliary)
Maximum output current
6 different circuits of 16 A per multi-pole connector.
16 A on the auxiliary connector.
Ruggedness
IP66 when all output multi pole connectors are occupied.
Weight (max)
Roughly 60 kg.
Dimensions (max)
600 x 300 x 1200 (W x D x H)
Regulation compliance
CE.
6
R5976620 CUSTOM POWER BOX 05/06/04