Table 4: Minimum dimension and clearance to flammable ceiling
With false ceiling
Without false ceiling
h
Area of the convection air
outlet opening
Minimum 300 mm
2
Minimum 50 cm open
space between ceiling and
chimney enclosure
H
Height of the false ceiling
minimum distance convec-
tion air outlet opening -
flammable ceiling
Minimum 50 cm (= 42.5 cm
free space + 75 mm false
ceiling)
Not applicable (the top side
of the chimney enclosure is
open with a clearance of
minimum 50 cm to the flam-
mable ceiling.
If a wooden beam is present above the appliance, make sure to protect it against direct
heat radiation. Make sure to put a non-flammable insulation plate with a thickness of
minimum 30 mm between the wooden beam and the appliance. with an air gap of
minimum 1 cm between the insulation plate and the wooden beam.
5.5
Clearances to non-flammable walls
Put a non-flammable insulation plate between the appliance and the rear wall and side
wall according
shows the minimum thickness of the insulation plates and the minimum
clearances to non-flammable materials and walls.
Attention: Make sure there is a 3 mm clearance between the appliance and
the surrounding construction, to allow for expansion of the appliance during
use.
Clearances
Unilux-7 75
17
Summary of Contents for Unilux-7 45
Page 1: ...Installation and maintenance manual Unilux 7 75 Serial number Production date...
Page 40: ...Figure 15 Dimensions of frameless appliance with steel frame door Dimensions 40 Unilux 7 75...
Page 49: ...Warranty Terms Unilux 7 75 49...
Page 50: ...Warranty Terms 50 Unilux 7 75...
Page 51: ...Warranty Terms Unilux 7 75 51...