 Installation & Operations

Blü-Test Wireless Test Instruments

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

rev. 08/16/21

41521_BluTest_G2_ins

9 of 12

•  Room Sensor measurement is done by holding the Blü-Test probe directly under the sensor enclosure for 3 minutes 

or until the reading stabilizes.  Body heat or breathing on the sensor is a major source of faulty readings, so holding 

the Blü-Test probe at the button end and standing away from the sensor is the best way to ensure a good 

measurement. The Probe Clip Hanger accessory (BA/PCH-1) simplifies this by holding the probe for you (Fig. 31).

•  Duct sensor measurement is done by drilling a 5/8” (15mm) hole in the duct near the duct sensor to be tested. Insert 

the Blü-Test probe in the hole so the tip is as close as possible to the duct sensor under test.  Hold the Blü-Test 

probe in place for 2 minutes or until the reading stabilizes. When finished, remove the probe and cover the test hole 

with duct tape.

•  Duct averaging sensor verification is more difficult. Use the probe clip hanger to clip the probe directly to the 

averaging sensor at 10 or more locations along its length. Leave the probe in place for 2 minutes or until the reading 

stabilizes.

•  Outside air sensor measurement requires that the Blü-Test probe be placed next to the outside air sensor.  This may 

require a ladder or extension pole.  Hold the Blü-Test probe in place for 3 minutes or until the reading stabilizes. The 

Probe Clip Hanger makes this easier by holding the probe for you (Fig. 32).

•  Walk-in freezer/cooler measurements require that the probe be placed in or around the product racks and not near 

the door. Do not let the probe tip touch the rack. The probe will require more time to stabilize due to the larger 

differential between room temperature and freezer/cooler temperature. Keep the probe in place for 15 to 20 minutes 

or until the reading stabilizes. The Probe Clip Hanger makes this easier by holding the probe for you (Fig. 33).

•  Immersion dry thermowell measurement can be done as long as the thermowell diameter is big enough. Remove the 

immersion sensor to be tested and place the Blü-Test Probe into the thermowell.  Hold the probe in place for 2 

minutes or until the reading stabilizes.

•  The piercing temperature probe is designed to be used with “Pete’s plugs”.  It is also designed to be used when 

piercing a medium is needed such as in insulation or soil.

Sect. 9: Best Measurement Practices

Fig. 31:

 Probe Clip 

Hanger used on a 

room sensor

Fig. 32:

 Probe Clip 

Hanger used on an 

outside air sensor

Fig. 33:

 Probe Clip 

Hanger used on a 

wire shelf

Summary of Contents for Blu-Test

Page 1: ...ows hands free measuring in ducts Reversible belt clip OLED displays measurements and cycles through other displays battery level log indicator etc Sealed probe tip can be used in liquids Gauge Graph...

Page 2: ...10 11 Storage 10 12 Diagnostics 10 13 Recalibration Information 10 14 Specifications 11 Bl Test is a suite of handheld test instruments that communicate via Bluetooth 4 2 to the user s enabled Android...

Page 3: ...ctivity no logging no active App present On Probe Log Storage Probe can store up to a million readings in a maximum of 31 log files Once the memory is full a new log file will automatically overwrite...

Page 4: ...r download from the probe to the Bl Test application Tap the top left Download button to download the checked files to your device or tap the white down arrow to download individual files The down arr...

Page 5: ...umidity log is selected as the primary log so the scale values on the axes only apply to that graph Sect 6 Application Logs Screen Overview Bl Test Application The Application Logs Screen different fr...

Page 6: ...sites and locations screens along with exporting a comma separated values csv file of your sites and locations Fig 15 Sites Screen before adding sites Fig 16 Sites Screen with site added Fig 17 Locati...

Page 7: ...ool will then provide the transmitter specifications including the accuracy at 8 and 16 mA accuracy at 25 50 and 75 of span linearity and power output shift The Tools Section of the Home Screen includ...

Page 8: ...he application discovers Changes to specific probes can still be made via the gauges view of the specific probe Resistance to Temperature This tool will calculate the temperature when you enter the re...

Page 9: ...Leave the probe in place for 2 minutes or until the reading stabilizes Outside air sensor measurement requires that the Bl Test probe be placed next to the outside air sensor This may require a ladde...

Page 10: ...1 The log file may be very large so give it time to download A week long log file can take up to 30 minutes to download from the probe to the application This is normal behavior Possible Problem iOS...

Page 11: ...sure Probes Low Range 0 25 of FS Span 1 to 1 WC 250 to 250 Pa at 77 F 25 C Standard Range 0 25 of FS Span 5 to 5 WC 1 250 to 1 250 Pa at 77 F 25 C Burst Pressure Differential Pressure Probes Low Range...

Page 12: ...735 4800 Fax 1 608 735 4804 E mail sales bapihvac com Web www bapihvac com Google Play and the Google Play logo are trademarks of Google LLC Apple and the Apple logo are trademarks of Apple Inc regis...