Sect. 14: Specifications
Power:
3.7V, 2,600 mAh Rechargeable Battery
Charging:
Standard USB Charger, 1.5A or greater, Micro-USB cable included
Measurement Range:
Temperature: -40 to 185°F (-40 to 85°C)
%RH: 5 to 95% Non-condensing @ -40 to 158°F (-40 to 70°C)
Differential Pressure Low Range: -1 to +1” WC (-250 to +250 Pascal) @ -4 to 158°F (-20 to 70°C)
Differential Pressure Standard Range: -5 to +5” WC (-1,250 to +1,250 Pascal) @ -4 to 158°F (-20 to 70°C)
Accuracy - Temperature Only Probes:
±0.18°F from -13 to 167°F (±0.1°C from -25 to 75°C)
Accuracy - Temp/Humidity Probes:
Temperature: ±0.36°F at 77°F (±0.2°C at 25°C)
%RH: ±1%RH at 77°F (25°C) from 10 to 85%RH
Accuracy - Differential Pressure Probes:
Low Range: ±0.25% of FS Span, -1 to +1” WC (-250 to +250 Pa) at 77°F (25°C)
Standard Range: ±0.25% of FS Span, -5 to +5” WC (-1,250 to +1,250 Pa) at 77°F (25°C)
Burst Pressure - Differential Pressure Probes:
Low Range: 415” WC (103 kPa) • Standard Range: 500” WC (124 kPa)
Communication:
Bluetooth LE, Class 2 v4.2
Data Logging:
10 second intervals
Environmental Operating Range:
Blü-Test Body: -22 to 158°F (-30 to 70°C)
Temperature Probes: -40 to 185°F (-40 to 85°C)
%RH Probe: 5 to 95% Non-condensing @ -40 to 158°F (-40 to 70°C)
Pressure Probe: -4 to 158°F (-20 to 70°C)
Agency:
CE EN 61326-1:2013 EMC, RoHS, NSF
FCC ID:
Contains FCC ID 2AA9B04
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device
may not cause harmful interference, and (2) this device must accept any interference received, including interference
that may cause undesired operation.
FCC Rules Part 15:
https://www.fcc.gov/media/radio/low-power-radio-general-information#PART15
Blü-Test App Specifications
Application Program:
Android OS 5.1 or Apple iOS 10 or higher required.
Specifications subject to change without notice.