Termination and Troubleshooting

Water Leak Detector (BA/LDT) 5 Amp Relays

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

rev. 09/01/21

26268_ins_LDT

6 of 6

Specifications subject to change without notice.

Specifications

Maintenance

Check the water sensor probe once a year to be sure there is no dirt or debris collected around the probes.  Dirt or 

debris around the probes may cause nuisance alarms in moist situations.  Change the service intervals depending 

on environmental conditions. In very clean conditions the probe may never need maintenance. Rope sensor may be 

wiped down with isopropyl alcohol, warm soapy water on a cotton cloth or placed in a dishwasher.

Power: 

24VAC ±10% (If VDC power is required, call your BAPI rep.), 5 Amp Relays: 4 Watt / 4 VA max

Rectification: 

Half Wave

Wiring:

Screw Terminals: 2 to 4 pair of 12 to 22AWG (BAPI recommends 16 to 22AWG). 

Water Detection Sensor: 2 wires (provided), optional Flex Connector or Liquid Tight Fitting for strain relief

Sensor: 

Rope Sensor: Plenum-rated sensor cable, detects 1/8” of water. Max length: 100’ (30.5m)

Attached Sensor: Sensor w/ adjustable depth screw from 0.063 to 0.84” (1.60 to 21.34mm) 

Remote Sensor: Sensor w/ adjustable depth screw from 0.062 to 0.5” (1.57 to 12.70mm) 

(Attached and Remote Sensors are designed to be mounted to flat surfaces or on the rims of drip pans.)

Latching and Supervised Relay Options:

 

Latching ............

Relay stays in alarm until manually reset or power is cycled

Non-Latching

 ....

Relay automatically resets after water is removed (default)

Unsupervised....

Relay energizes on water detection

Supervised

........

Relay de-energizes on water detection (default) Note: Relay de-energizes on loss of power

Reset Action:

 If latching, local pushbutton or power interrupt

Local Indication: 

One green power LED, one red alarm LED

Alarm Relay Contacts:

LDT3: One SPDT, 5 Amp relay output

LDT4: Two SPDT, 5 Amp relay outputs

Operating Environment

Remote Sensor: -20 to 185ºF (-20 to 70ºC), 0 to 100%RH, condensing

Rope Sensor: 32 to 167ºF (0 to 75ºC), 0 to 95%RH, non-condensing

Detector (BB): -4 to 158ºF (-20 to 70ºC), 0 to 95%RH, non-condensing

Enclosure Material and Ratings: 

NEMA 4 (IP66), UV-resistant polycarbonate, UL94 V-0 

Agency: 

RoHS, UL

Warranty:

 5 years

Diagnostics

Possible Solution

1. Check for proper power to the unit (see power specs).
1. Check for proper power to the unit (see power specs).

2. Physically check for water to verify it’s touching both screws on the Attached 

Sensor or Remote Spot, or touching the Rope Sensor.

3. Adjust sensor probe depth on the Attached Sensor or Remote Spot if necessary.

4. For Rope Sensor units, check the sensitivity adjustment as described on page 4.

1. Check for the presence of water or debris on the sensor.

2. Be sure the sensor wires are not shorted.

3. Push the reset button and/or cycle power.

4. For rope sensor units, check the sensitivity adjustment as described on page 4.

Possible Problem

Green LED Not On

Red LED Not 

Working Or Alarm 

Contact Not 

Changing State

Unit Will Not Reset