background image

Termination and Troubleshooting

Water Leak Detector (BA/LDT) 5 Amp Relays

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

rev. 09/01/21

26268_ins_LDT

3 of 6

Fig. 10:

Rope Sensor 

Hot Water Tank 

Pan Mounting

Mounting continued...

Fig. 11:

 Sub-Floor Rope Sensor Mounting

Fig. 12:

 Horizontal Pipe Rope Sensor Mounting

Fig. 13:

Vertical Pipe 

Rope Sensor 

Mounting

Combining Sensors

The following combinations of sensors can be used:
1. Two rope sensors with a combined length of no more 

than 100ft (30.m).

2. Two spot sensors with a combined length of no more 

than 75ft (22.8m).

3. One spot sensor with a maximum length of 25ft (7.6m) 

and one rope sensor of no more than 50ft (15.2m).

Secure Rope 

Sensor directly 

to floor every 

5ft. It is 

important that 

the rope be 

pulled tight so 

it lays flat on 

the floor. 

Rope Sensor Mounting Bracket

The BAPI Rope Sensor Mounting 

Bracket is specifically designed to 

hold the rope taut and prevent rope 

slippage allowing for maximum contact with the 

monitored surface. Bracket can be easily mounted 

to flat surfaces utilizing the industrial adhesive 

backing or the built in screw holes. 

Part Number: BA/LDT-RR-MB

Reviews: