Termination and Troubleshooting
Water Leak Detector (BA/LDT) 5 Amp Relays
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
rev. 09/01/21
26268_ins_LDT
3 of 6
Fig. 10:
Rope Sensor
Hot Water Tank
Pan Mounting
Mounting continued...
Fig. 11:
Sub-Floor Rope Sensor Mounting
Fig. 12:
Horizontal Pipe Rope Sensor Mounting
Fig. 13:
Vertical Pipe
Rope Sensor
Mounting
Combining Sensors
The following combinations of sensors can be used:
1. Two rope sensors with a combined length of no more
than 100ft (30.m).
2. Two spot sensors with a combined length of no more
than 75ft (22.8m).
3. One spot sensor with a maximum length of 25ft (7.6m)
and one rope sensor of no more than 50ft (15.2m).
Secure Rope
Sensor directly
to floor every
5ft. It is
important that
the rope be
pulled tight so
it lays flat on
the floor.
Rope Sensor Mounting Bracket
The BAPI Rope Sensor Mounting
Bracket is specifically designed to
hold the rope taut and prevent rope
slippage allowing for maximum contact with the
monitored surface. Bracket can be easily mounted
to flat surfaces utilizing the industrial adhesive
backing or the built in screw holes.
Part Number: BA/LDT-RR-MB