3. Gently unplug the ribbon cable from the board mounted into the bottom housing. For Class I, Division 2 certified devices, skip this
step (the ribbon cable is glued).
4. Remove the black cover plate from the bottom of the device's cover.
The DIP switches are located behind the rotary dials. After making the neces-
sary changes to the DIP switches, place the black cover plate back into posi-
tion and gently push into place. Plug the ribbon cable in after verifying that
the blocked hole lines up with the missing pin. Mount the cover back onto the
housing.
DIP Switch Settings
Switches
Device Settings
1
2
3
4
5
6
7
8
Rotary switch address mode
OFF*
Extended address mode
ON
Temp °Fahrenheit
OFF*
Temp °Celsius
ON
High resolution (0.1 degree)**
OFF*
Low resolution (1 degree)
ON
Discrete sinking inputs
OFF*
Discrete sourcing inputs
ON
Thermocouple, J-Type
OFF*
OFF*
OFF*
OFF*
Thermocouple, B-Type
OFF
OFF
OFF
ON
Thermocouple, C-Type
OFF
OFF
ON
OFF
Thermocouple, D-Type
OFF
OFF
ON
ON
Thermocouple, E-Type
OFF
ON
OFF
OFF
Thermocouple, G-Type
OFF
ON
OFF
ON
Thermocouple, K-Type
OFF
ON
ON
OFF
Thermocouple, L-Type
OFF
ON
ON
ON
Thermocouple, M-Type
ON
OFF
OFF
OFF
Thermocouple, N-Type
ON
OFF
OFF
ON
Thermocouple, P-Type
ON
OFF
ON
OFF
Thermocouple, R-Type
ON
OFF
ON
ON
Thermocouple, S-Type
ON
ON
OFF
OFF
Thermocouple, T-Type
ON
ON
OFF
ON
Thermocouple, U-Type
ON
ON
ON
OFF
Host configured (overrides DIP switches)
ON
ON
ON
ON
* Default configuration
SureCross DX80 FlexPower Thermocouple Node