7. Install your wireless sensor network components. If installation instructions are not included in this datasheet, refer to the product
manual for detailed installation instructions.
For additional information, including installation and setup, weatherproofing, device menu maps, troubleshooting, and a list of accesso-
ries, refer to one of the following product manuals.
• SureCross Quick Start Guide: Banner part number
• SureCross Wireless I/O Network Manual:
• Web Configurator Manual (used with "Pro" and DX83 models):
Configuring the DIP Switches
Before making any changes to the DIP switch positions, disconnect the power. DIP switch changes will not be recognized if power isn't
cycled to the device.
For parameters not set via DIP switches, use the User Configuration Tool (UCT) to make configuration changes. For parameters set
using the DIP switches, the DIP switch positions override any changes made using the User Configuration Tool.
Accessing the Internal DIP Switches
To access the internal DIP switches, follow these steps:
1. Unscrew the four screws that mount the cover to the bottom housing.
2. Remove the cover from the housing without damaging the ribbon cable or the pins the cable plugs into.
3. Gently unplug the ribbon cable from the board mounted into the bottom housing.
4. Remove the black cover plate from the bottom of the device's cover.
The DIP switches are located behind the rotary dials.
After making the necessary changes to the DIP switches, place the black cover plate back into position and
gently push into place. Plug the ribbon cable in after verifying that the blocked hole lines up with the missing
pin. Mount the cover back onto the housing.
DIP Switch Settings
Switches
Device Settings
1
2
3
4
5
6
7
8
Rotary switch address mode
OFF*
Extended address mode
ON
Modbus or UCT configured (overrides DIP
switches 3-8)
OFF*
DIP switch configured
ON
Inputs sourcing (PNP)
OFF*
Inputs sinking (NPN)
ON
Link loss output: zero
OFF*
OFF*
Link loss output: one
OFF
ON
Link loss output: hold last state
ON
OFF
Link loss output: user configuration
ON
ON
* Default configuration
SureCross DX80 Node
2
www.bannerengineering.com - tel: 763-544-3164
P/N 131293 Rev. F