Remote Configuration
The remote function can be used to configure the sensor remotely or to disable the push button for security. Connect the
gray wire of the sensor to ground (0 V dc), with a remote programming switch connected between them. Pulse the remote
line according to the diagrams in the configuration procedures. The length of the individual programming pulses is equal to
the value T where: 0.04 seconds
≤
“T”
≤
0.8 seconds
Installation
Wiring Diagrams
Cabled Models
QD Models
bn
Remote
Teach
bu
wh
bk
gy
+
10-30V dc
–
Load
Load
bn
Remote
Teach
bu
wh
bk
gy
+
10-30V dc
–
Load
Load
Glass Fiber Installation
O-ring
Retaining Clip
1. Install the O-ring (supplied with the fiber) on each fiber end, as
shown in the drawing.
2. While pressing the fiber ends firmly into the ports on the sensor
front, slide the U-shaped retaining clip (supplied with the sensor)
into the slot in the sensor's barrel, until it snaps into place.
Plastic Fiber Installation
Trimmed fiber
control ends
Plastic fiber
emitter port
Plastic fiber
receiver port
Gripper
Unlock
Lock
Adapters for
0.25- and 0.5-mm fibers
Sensor Face
1. With supplied fiber cutter, make a clean cut at the control
ends of fibers.
2. Unlock the fiber gripper as shown in the drawing.
3. Apply appropriate fiber adaptors to the fiber, if needed.
4. Gently insert the prepared fiber ends into the ports as far
as they will go.
5. Slide the fiber gripper back to lock, as shown in the
drawing.
MINI-BEAM Expert Series
P/N 68812 Rev. C
www.bannerengineering.com - Tel: +1-763-544-3164