7 Preparing for System Operation
After the initial trip test has been accomplished, and the OSSD safety outputs and EDM connections have been made to the
machine to be controlled, the EZ-SCREEN LPM is ready for testing in combination with the guarded machine.
The operation of the EZ-SCREEN LPM with the guarded machine must be verified before the combined System and
machine may be put into service. To do this, a Qualified Person must perform the Commissioning Checkout Procedure (see
(p. 50)).
7.1 Commissioning Checkout
WARNING:
• Do not use the system until the checkouts are verified
• Attempts to use the guarded/controlled machine before these checks are verified could result in
serious injury or death.
• If all these checks cannot be verified, do not attempt to use the safety system that includes the
Banner device and the guarded/controlled machine until the defect or problem has been
corrected.
Perform this checkout procedure as part of the System installation after the System has been interfaced to the guarded
machine, or whenever changes are made to the System (either a new configuration of the EZ-SCREEN LPM or changes to
the machine). A Qualified Person must perform the procedure. Checkout results should be recorded and kept on or near the
guarded machine as required by applicable standards.
To prepare the System for this checkout:
1. Examine the guarded machine to verify that it is of a type and design compatible with the EZ-SCREEN LPM System.
See for a list of appropriate and inappropriate applications.
2. Verify that the EZ-SCREEN LPM is configured for the intended application.
3. Verify that the safety distance (minimum distance) from the closest danger point of the guarded machine to the
defined area is not less than the calculated distance, per
Calculating the Safety Distance (Minimum Distance)
4. Verify that:
• Access to any dangerous parts of the guarded machine is not possible from any direction not protected by
the EZ-SCREEN LPM System, hard (fixed) guarding, or supplemental safeguarding, and
• It is not possible for a person to stand between the defined area and the dangerous parts of the machine, or
• Supplemental safeguarding and hard (fixed) guarding, as described by the appropriate safety standards, are
in place and functioning properly in any space (between the defined area and any hazard) which is large
enough to allow a person to stand undetected by the EZ-SCREEN LPM.
5. If used, verify that all reset switches are mounted outside and in full view of the guarded area, out of reach of
anyone inside the guarded area, and that means of preventing inadvertent use is in place.
6. Examine the electrical wiring connections between the EZ-SCREEN LPM OSSD outputs and the guarded machine’s
control elements to verify that the wiring meets the requirements stated in
Electrical Connections to the Guarded
(p. 42).
7. Inspect the area near the defined area (including work pieces and the guarded machine) for reflective surfaces (see
(p. 23)). Remove the reflective surfaces if possible by relocating them, painting,
masking or roughening them. Remaining problem reflections will become apparent during the Trip Test.
8. Verify that power to the guarded machine is Off. Remove all obstructions from the defined area. Apply power to the
EZ-SCREEN LPM System.
9. Observe the Status indicators and Diagnostic Display:
• Lockout: Status flashing red; all others Off
• Blocked: Status On red; one or more Zone indicators On red; Reset On amber
• Clear: Status On green
9
; all Zone indicators On green
10
; Reset On amber
• Latch: (defined area clear) Status On red; all Zone indicators On green; Reset double-flashing amber
Perform a manual reset as described in
(p. 76).
10. A Blocked condition indicates that one or more of the beams is misaligned or interrupted. See the Optical Alignment
procedure in the
(p. 34) section to correct this situation. If the System is in a Latch
condition, perform a manual reset.
9
The status indicator flashes green if reduced resolution is enabled.
10
The Zone indicators flash green if fixed blanking is enabled.