X20(c)SC2212
6
Data sheet V1.141 X20(c)SC2212 Translation of the original documentation
Model number
X20SC2212
X20cSC2212
Switching voltage
I/O power supply minus residual voltage
Total nominal current
120 mA
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation elevation above sea level
0 to 2000 m, no limitation
Degree of protection per EN 60529
IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation
0 to 60°C
-40 to 60°C
3)
Vertical mounting orientation
0 to 50°C
-40 to 50°C
4)
Derating
See section "Derating".
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Up to 100%, condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical properties
Note
Order 1x safety-keyed terminal block separately.
Order 1x safety-keyed bus module separately.
Spacing
25
+0.2
mm
Table 5: X20SC2212, X20cSC2212 - Technical data
1)
The related danger warnings in the technical data sheet must also be observed.
2)
The protective function is provided for max. 30 minutes for a continuous short circuit.
3)
Up to hardware upgrade <1.10.1.0 and hardware revision <E0: -25 to 60°C
4)
Up to hardware upgrade <1.10.1.0 and hardware revision <E0: -25 to 50°C
Danger!
Operation outside the technical data is not permitted and can result in dangerous states.
Information:
For detailed information about installation, see chapter
"Installation notes for X20 modules" on page
.
Derating
The derating curve refers to standard operation and can be shifted to the right by the specified derating bonus if
in a horizontal mounting orientation.
Module
X20SC2212
Derating bonus
At 24 VDC
+5°C
Dummy module on the left
+2.5°C
Dummy module on the right
+0°C
Dummy module on the left and right
+5°C
With double PFH / PFH
d
+0°C
Table 6: Derating bonus