X20(c)SC2212
30
Data sheet V1.141 X20(c)SC2212 Translation of the original documentation
Danger!
With "Disable_OSSD = Yes-ATTENTION", the module has reduced error detection capabilities and no
longer meets the requirements for SIL 3 per EN 62061:2010 or PL e per EN ISO 13849-1:2015.
In order to meet the requirements for applications up to SIL 2 per EN 62061:2010 or PL d per
EN ISO 13849-1:2015, a daily check of the safety function by the user is necessary.