16.4 Channel list
Channel name
Access via Au-
tomation Studio
Access via
SafeDESIGNER
Data type
Description
ModuleOk
Read
-
BOOL
Indicates if the module is OK
SerialNumber
Read
-
UDINT
Module serial number
ModuleID
Read
-
UINT
Module ID
HardwareVariant
Read
-
UINT
Hardware variant
FirmwareVersion
Read
-
UINT
Firmware version of the module
UDID_low
(Read)
1)
-
UDINT
UDID, lower 4 bytes
UDID_high
(Read)
1)
-
UINT
UDID, upper 2 bytes
SafetyFWversion1
(Read)
1)
-
UINT
Firmware version - Safety processor 1
SafetyFWversion2
(Read)
1)
-
UINT
Firmware version - Safety processor 2
SafetyFWcrc1
(hardware upgrade 1.10.1.0 or
later)
(Read)
1)
-
UINT
CRC of firmware header on safety processor 1
SafetyFWcrc2
(hardware upgrade 1.10.1.0 or
later)
(Read)
1)
-
UINT
CRC of firmware header on safety processor 2
Bootstate
(hardware upgrade 1.10.1.0 or
later)
(Read)
1)
-
UINT
Startup state of the module.
Notes:
•
Some of the boot states do not occur during normal
startup or are cycled through so quickly that they
are not visible externally.
•
The boot states usually cycle through in ascending
order. There are cases, however, in which a previ-
ous value is captured.
Value
Description
0x0003
Startup communication processor OK, no
communication to the safety processors
(check 24 V supply voltage!)
0x0010
FAILSAFE. At least one of the safety proces-
sors is in the safe state.
0x0020
Internal communication to safety processors
started
0x0024
Firmware update of safety processors
0x0040
Firmware of safety processors started
0x0440
Firmware of safety processors running
0x0840
Waiting for openSAFETY "Operational" (load-
ing SafeDESIGNER application or no valid
application exists, waiting on acknowledg-
ments such as module exchange)
0x1040
Evaluating the configuration according to the
SafeDESIGNER application
0x3440
Stabilizing cyclic openSAFETY data ex-
change.
Note:
If the boot state remains here, check
SafeDESIGNER parameters "(Default) Safe
Data Duration", "(Default) Additional Tolerated
Packet Loss".
0x4040
RUN. Final state, startup completed.
Diag1_Temp
(Read)
1)
-
INT
Module temperature in °C
PLCopenFBKxy_state
Read
-
USINT
State number of dual-channel evaluation (PLCopen
function block "Equivalent" or "Antivalent")
InputErrorStates
(Read)
1)
-
UDINT
Channel status, additional information for channel error
Type of error
Inputs
Input stuck at high
Bit no. 0 to 5 = Channel 1 to 6
If a bit is set, the corresponding error has
been detected on the respective channel.
PulseoutputErrors
(Read)
1)
-
UDINT
Channel status, additional information for channel error
Type of error
Pulse outputs
Feedback stuck at high
(shorted to 24 VDC)
Feedback stuck at
low (ground fault)
Bit no. 8 to 13 =
Channel 1 to 6
Bit no. 0 to 5 =
Channel 1 to 6
If a bit is set, the corresponding error has
been detected on the respective channel.
SafeModuleOK
-
Read
SAFEBOOL
Indicates if the safe communication channel is OK
Table 26: Channel list