Technical data • Fully assembled device
Chapter 2
Technical data
Automation PC 810 with GM45 CPU board user's manual V1.28
27
2.1.1 Maximum ambient temperature with fan kit
Information:
•
Vertical and horizontal (minus 5°C) mounting orientations are permitted (1.3 "Mounting orien-
tation" on page 171).
•
The specifications in the following table are only valid for system units with the heat sink
5AC801.HS00-01 ≥ Rev. D0.
T9400
P8400
All temperature values in degrees
Celsius (°C) at 500 m above sea level.
The maximum ambient temperature is typically derated by
1°C per 1000 meters (starting at 500 meters above sea level).
5PC800.BM45-00
5PC800.BM45-01
Maximum ambient temperature
1)
50
55
What else can also be operated at the max.
ambient temperature, or are there any limits?
Temperature limits
Location of sensor(s)
Onboard CompactFlash
2)
✓
✓
80
5AC801.HDDI-00
✓
✓
80
5AC801.HDDI-02
✓
✓
80
5AC801.HDDI-03
✓
50
60
5AC801.HDDI-04
✓
50
60
5AC801.SSDI-00
✓
✓
70
5AC801.SSDI-01
✓
✓
70
5AC801.SSDI-02
✓
✓
70
Slide-in compact drives
5AC801.SSDI-03
✓
✓
70
I/O
5AC801.HDDS-00
✓
✓
80
5AC801.DVDS-00
✓
✓
50
Slide-in drives
5AC801.DVRS-00
✓
✓
50
Slide- in drive
5MMDDR.2048-02
✓
✓
-
Main memory
5MMDDR.4096-02
✓
✓
-
-
5PC810.SX01-00
✓
✓
80
5PC810.SX02-00
✓
✓
80
5PC810.SX03-00
✓
✓
80
System units
5PC810.SX05-00
✓
✓
80
Power supply
5AC600.CANI-00
✓
✓
-
5AC600.485I-00
✓
✓
-
5AC801.SDL0-00
✓
✓
-
5AC801.RDYR-00
✓
✓
-
5ACPCI.RAIC-03 (24 hours / standard)
✓
✓
-
5ACPCI.RAIC-05 (24 hours / standard)
✓
50
-
Additional insert cards
Interfaces / AP Link
5ACPCI.RAIC-06 (24 hours / standard)
✓
50
-
-
1) With horizontal mounting, the maximum ambient temperature must be reduced by 5°C!
2) Only possible with a CompactFlash card from B&R that is compatible with the device.
Table 5: Ambient temperature with a fan kit
2.1.1.1 How is the maximum ambient temperature determined?
1. The CPU board is selected (i.e. operation with or without a fan kit).
2. The "Maximum ambient temperature" row shows the maximum ambient temperature for the fully assembled
device, including the respective CPU board.
Information:
Maximum temperature data is for operation at 500 meters. The maximum ambient temperature is
typically derated by 1°C per 1000 meters (starting at 500 meters above sea level).
3. Incorporating additional drives (add-on, slide-in), main memory, additional insert cards, etc. can change the
temperature limits of an APC810 system.
If there is a
"✓"
next to the component, it can be used at the maximum ambient temperature of the fully assembled
device without problems.
If there is a specific temperature, for example "35", next to the component, then the ambient temperature of the
fully assembled APC810 system cannot exceed this temperature.