Technical data • Individual components
Chapter 2
Technical data
Automation PC 510 User's Manual V 1.01
55
Resolution
SDL cables
Segment length [m]
VGA
640 x 480
SVGA
800 x 600
XGA
1024 x 768
SXGA
1280 x 1024
UXGA
1600 x 1200
FHD
1920 x 1080
20
5CASDL.0200-00
5CASDL.0200-03
5CASDL.0200-00
5CASDL.0200-03
5CASDL.0200-00
5CASDL.0200-03
5CASDL.0200-00
5CASDL.0200-03
-
-
-
5CASDL.0200-03
25
5CASDL.0250-00
5CASDL.0250-03
5CASDL.0250-00
5CASDL.0250-03
5CASDL.0250-00
5CASDL.0250-03
-
-
-
-
-
-
30
5CASDL.0300-00
5CASDL.0300-03
5CASDL.0300-00
5CASDL.0300-03
-
5CASDL.0300-13
-
5CASDL.0300-13
-
-
-
5CASDL.0300-13
40
5CASDL.0400-13
5CASDL.0400-13
5CASDL.0400-13
5CASDL.0400-13
-
5CASDL.0400-13
Table 58: Cable lengths and resolutions for SDL transfer
Serial interface COM2
Serial interface COM2
RS232
RS422/485
Type
RS232; not modem capable; electrically isolated
UART
16550-compatible, 16-byte FIFO
Transfer rate
Max. 115 kbit/s
Bus length
Max. 15 m
Max. 1200 m
Pin
RS232 pinout
RS422 pinout
1
n.c.
TXD\
2
RXD
n.c.
3
TXD
n.c.
4
n.c.
TXD
5
GND
GND
6
n.c.
RXD\
7
RTS
n.c.
8
CTS
n.c.
9
n.c.
RXD
9-pin DSUB socket
5
1
9
6
Table 59: Pinout - COM2
I/O address and IRQ
Resource
Default setting
Additional setting options
I/O address
2E8h
238h, 2F8h, 328h, 338h, 3E8h, 3F8h
1)
IRQ
10
3, 4, 5, 6, 11, 12
1)
Table 60: RS232/422/485 - I/O address and IRQ
1)
If these settings are not already used in the system.
Bus length and cable type RS232
The maximum transfer rate of 115 kbit/s depends on the cable type being used.
Extension
Transfer rate
≤ 15 m
Typ. 64 kbit/s
≤ 10 m
Typ. 115 kbit/s
≤ 5 m
Typ. 115 kbit/s
Table 61: RS232 - Bus length and transfer rate
The material used for the cable should preferably have all or most of the following properties in order to reach an
optimal transfer rate.
RS232 cable
Property
Signal lines
Cable cross section
Wire insulation
Conductor resistance
Stranding
Shield
4x 0.16 mm² (26AWG), tinned Cu wire
PE
≤ 82 Ω/ km
Wires stranded in pairs
Paired shield with aluminum foil
Grounding line
Cable cross section
Wire insulation
Conductor resistance
1x 0.34 mm² (22AWG/19), tinned Cu wire
PE
≤59 Ω/km
Outer sheathing
Material
Features
Cable shielding
PUR mixture
Halogen free
From tinned cu wires
Table 62: RS232 - Cable requirements