Technical data
Mobile Panel 7100 User's manual 1.51
17
2.2.1.3 Device interfaces
Interfaces are located on the bottom of Mobile Panel 715x and Mobile Panel 7140 and on the side of Mobile Panel
712x.
•
Ethernet (10/100 Mbit)
•
USB host for connecting various USB flash drives (MP7140 and MP715x)
•
USB host for connecting USB OTG adapter cable (MP712x)
IP65 protection can only be achieved if the USB protective cover is properly installed.
2.2.1.3.1 +24 VDC power supply
The power supply is provided with an individually selected attachment cable (see
) and control cabinet cable (see
"Control cabinet cables" on page 62
). Alternatively, a large connection
box (4MPCBX.0000-00) with associated box cable (see
) can be used.
For the pinout, see the description of the corresponding cable type.
Danger!
•
The device is only permitted to be supplied with a SELV/PELV power supply or with safety
extra-low voltage (SELV) per EN 60950.
•
Safety extra-low voltage circuits must always be safely isolated from circuits with dangerous
voltage.
•
In the end application, the 24 VDC power supply of the device must be adequately protected! A
fuse with max. 3.15 A and UL 248 certification must be used for this.
2.2.1.3.2 Ethernet interface
The Ethernet interface is located inside the device. The connection is made via the connector integrated in the
connection cable or control cabinet cable.
Ethernet interface (ETH)
Variant
RJ45, female
Wiring
Up to star-quad cables
Transfer rate
10/100 Mbit/s
1)
Cable length
Max. 20 m (min. Cat 5e)
-
1)
Switching takes place automatically.
Information:
Necessary drivers must be downloaded from the B&R website, not from manufacturer websites.