14.4 Troubleshooting for Gas Valves
14.5 Troubleshooting for Flue Blower
Valve faulty.
Replace with one of
correct type.
Fault elsewhere.
Correct pressure problem.
If problems persist, contact
Bananza at
www.bananza.com
Valve Operating
TROUBLESHOOT ENDS.
No
Yes
Valve or ignition control
faulty. Replace with
one of correct type.
Does gas pressure at
outlet of valve return to zero or
lower when valve turns off?
No
Yes
Does gas pressure at outlet
of the valve rise when
valve turns on?
No
Yes
Is gas pressure at inlet of the
valve correct for gas type?
Note pressure found.
No
Yes
START
For optimum heater performance, use only replacement parts sold and supplied by Bananza.
Conduct start-up procedure as shown
on Page 28, Section 11
.
If problems persist, contact
Bananza at
www.bananza.com
Fan Operating
TROUBLESHOOT ENDS.
No
Fan motor faulty.
Replace with correct type.
Check fan motor leads for
loose connections.
Correct power
supply problem.
Yes
START
Does fan turn on and
off while burner is firing
continously?
No
Yes
Does combustion fan run
automatically when there
is a call for heat?
No
Yes
Summary of Contents for UHD 150 series
Page 2: ......
Page 4: ......
Page 8: ......
Page 27: ...SECTION 9 GAS PIPING 19 of 55 Figure 13 Gas Connection ...
Page 47: ...SECTION 14 TROUBLESHOOTING 39 of 55 14 1 General ...
Page 62: ...UHD STANDARD DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL 54 of 55 ...
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......