CAUTION

Installation, initial start-up and maintenance may only be performed by trained personnel. All applicable European and national
regulations regarding installation of electrical equipment must be adhered to. 
- The device may only be connected to supply power which complies with the specifications included in the technical data and on 

the serial plate. 

- The device must be disconnected from all sources of power during installation and maintenance work! 
- The device may only be operated under the conditions specified in the operating instructions!

DESCRIPTION

The MAXIMAT LW CZ ... compact leakage sensor is used as a leakage monitoring device for permanently installed containers used for
the storage of non-flammable, water endangering liquids.It is equipped with three different output circuits: 
- A binary output for controlling a coupling relay or the digital input at a PLC 
- A 0 to 20 mA current output for controlling an analog input channel, e.g. a programmed logic controller (PLC) 
- Self-monitoring measuring circuit in combination with the MAXIMAT SHR C... measuring transducer with 2-wire connection

Applications: 

Note that stored liquids may not tend to precipitate insulating or conductive sediments.C.s.

CE mark: 

In accordance with low-voltage directive (73/23/EWG), EMC directive (89/336/EWG) and EN 50 082-2:1995, EN 55

011 (class A):1998C.

TECHNICAL FEATURES

Supply power: 

24 V DC ± 10%
CAUTION: power supply with current limiting or 250 mA fuse recommended

Connected load: 

Approx. 3 W

Ambient temperature: 

-20 to +60° C

Container pressure: 

Atmospheric (0.8 to 1.1 bar)

Hysteresis: 

About 2 mm

Switching height: 

5 mm as the minimum

Connecting cable:

6 m long PCV cable
shielded, 7x0,5 mm

2

for MAXIMAT LWC. 

shielded, 7x0,34 mm

2

for MAXIMAT LWC25 

Outputs:

– Binary output: +DO / -DO max. 30 mA at 24 V DC
– Current output: +AO / -AO, 0 to 20 mA
– Output for MAXIMAT SHR C... measuring transducer

Terminals:

Housing: IP 65 – PBT – EN 60529
Screw terminals, IP 20 for MAXIMAT LW CZD and K
Maximum wire cross-section: 2.5 mm

2

DIP Switch: Operating 

Mode 

DIP1 

DIP2 

DIP3 

DIP4

Binary output 

ON 

ON 

ON 

OFF

Current output 

OFF 

OFF 

OFF 

OFF

MAXIMAT SHR C 

OFF * 

OFF * 

OFF * 

OFF *

* = Default setting

CAUTION: be sure to examine the DIP switch settings before switching supply power on!

Indicators: 

Green LED on the connector PCB:
Run = LED illuminated
Alarm / error = LED off

Measuring circuit for use with SHR C...

Cable inductance: 

Maximum approx. 5 mH

Cable capacitance: 

Maximum approx. 0.5 μF

Measuring circuit cable

Length: 

Maximum 300 m

Wire cross-section: 

Minimum 0.5 mm

2

DIBT Approval

Approval no. Z-65.40-316 for overfill inhibitors and leakage sensors in accordance with WHG §19

Note: 

The accompanying “General Building Supervisory Approval no. Z-65.40-316” is an integral part of the operating instructions

and all stipulations contained therein must be adhered to ! 