SIGNALING
LED (green) on the connection board (only for version with connection head):
Operation
LED lights up
Alarm / Fault
LED off
MAINTENANCE
When used as intended, the device is maintenance-free.
FUNCTION TEST: before installation / during commissioning / during revisions
Method 1
Measuring sensor
C
E
The bucket is on the floor.
• Fill a bucket (plastic or metal) with the process medium or water (at least 5 liters)
and place it on the floor
• Immerse the sensor several times and remove it again!
• Check the switching state of the measuring circuit!
Method 2
Ground connection:
- Protective conductor
foundation earth electrode
- Metal railing
- Metal water pipe
- Metal support pillar
etc.
Cable/strand for grounding the medium
The bucket is not on the floor.
• Fill a bucket (plastic or metal) with the process medium or water (at least 5
liters)!
• Ground the filled medium with a cable or stranded wire!
• Or grab the bucket with your hand from the outside!
• If the process medium is not harmful to health, a finger can also be held in the
medium. When doing so, immerse the sensor several times and remove it again!
• Check the switching state of the measuring circuit!
LEV
30-05-2023
M-556.06-EN-AC
556-06
/2
Compact overfill detector