ENGLISH
22 / 54
0006081544_201907
The switch on stage is thus repeated and, if the flame ignites
again normally, the burner starts working again normally, if not
(if the flame is irregular or fails to light completely) the equipment
goes automatically into lock-out (LED 5 comes on).
If the program is interrupted (due to a power supply failure, manual
action or the intervention of the thermostat, etc.) during the pre-
wash stage, the programmer returns to its starting position and will
automatically repeat the whole of the burner ignition sequence.
CAUTION / WARNINGS
The selection of the nozzles in function of the desired total
flow rate (2 nozzles in operation) must be made accounting
for the flow rate values that correspond to the diesel
operating pressure of 12 bar. Replacing the nozzles it is
possible to change considerably the ratio between first and
second stage.
The burner's hydraulic circuit is equipped with a solenoid valve
and a by-pass adjusting valve for a smooth vibration-less ignition
when operating with liquid fuel.
A part of diesel is thus drained only during the first 3-4 seconds
of operation of the burner. Once ignition is complete, the by-pass
solenoid valve closes and the rate corresponds to the first stage
value.
Use a screwdriver on the by-pass adjusting screw located inside
the cap (16), (screw in to increase the pressure) so as to obtain
only during the ignition stage a pressure of approx. 9 bars,
measured by connecting a pressure gauge in position (17).
Correct if necessary the corresponding amount of combustion air
by acting on the electronic equipment settings.
3 6
4
5
2
7
9
1
8
10
Displa
y_TBML_80pn
1 ON / OFF main switch
2 Voltage warning light
3 Fan operation warning light
4 2nd stage LED
5 Transformer ON led
6 1st stage operation warning light
7 Equipment shut-down warning light
8 Equipment release button
9 Fuel loading button
10 Fuel selector switch
0002570210funz
TBML 260 / 360..
16
17
16
Cap for by-pass adjusting screw
17
Pump pressure gauge connection.
Summary of Contents for TBML 200 MC
Page 2: ......
Page 48: ...ITALIANO 46 54 0006081544_201907 SCHEMI ELETTRICI ...
Page 49: ...ITALIANO 47 54 0006081544_201907 ...
Page 50: ...ITALIANO 48 54 0006081544_201907 ...
Page 52: ...ITALIANO 50 54 0006081544_201907 ...
Page 53: ...ITALIANO 51 54 0006081544_201907 ...
Page 54: ...ITALIANO 52 54 0006081544_201907 ...
Page 56: ...ITALIANO 54 54 0006081544_201907 ...
Page 102: ...ENGLISH 46 54 0006081544_201907 WIRING DIAGRAMS ...
Page 103: ...ENGLISH 47 54 0006081544_201907 ...
Page 104: ...ENGLISH 48 54 0006081544_201907 ...
Page 106: ...ENGLISH 50 54 0006081544_201907 ...
Page 107: ...ENGLISH 51 54 0006081544_201907 ...
Page 108: ...ENGLISH 52 54 0006081544_201907 ...
Page 110: ...ENGLISH 54 54 0006081544_201907 ...
Page 111: ......