TECHNICAL SPECIFICATIONS
MODEL
TBL 45P
TBL 45P DACA
TBL 60P
TBL 60P DACA
MINIMUM THERMAL CAPACITY
Kg/h
13.5
13.5
21.1
21.1
MAXIMUM THERMAL CAPACITY
Kg/h
37.9
37.9
50.6
50.6
MINIMUM THERMAL POWER
kW
160
160
250
250
MAXIMUM THERMAL POWER
kW
450
450
600
600
EMISSIONS
mg/
kWh
< 185 (Class II
according to EN
267)
< 185 (Class II
according to EN
267)
< 185 (Class II
according to EN
267)
< 185 (Class II
according to EN
267)
VISCOSITY
1.5° E - 20° C
1.5° E - 20° C
1.5° E - 20° C
1.5° E - 20° C
OPERATION
Two-stage
Two-stage
Two-stage
Two-stage
IGNITION TRANSFORMER
50 Hz
26 kV - 48 mA
26 kV - 48 mA
26 kV - 48 mA
26 kV - 48 mA
IGNITION TRANSFORMER
60 Hz
26 kV - 48 mA
26 kV - 48 mA
26 kV - 48 mA
26 kV - 48 mA
50 Hz FAN MOTOR
kW
0.5
0.5
0.65
0.65
60Hz FAN MOTOR
kW
0.5
0.5
0.65
0.65
ABSORBED ELECTRICAL POWER* 50Hz
kW
0.59
0.59
0.74
0.74
ABSORBED ELECTRICAL POWER* 60Hz
kW
0.59
0.59
0.74
0.74
50 Hz POWER SUPPLY VOLTAGE
1N~ 230V ± 10%
1N~ 230V ± 10%
3N~ 400V ± 10%
3N~ 400V ± 10%
60 Hz POWER SUPPLY VOLTAGE
1N~ 220V ± 10%
1N~ 220V ± 10%
3N~ 380V ± 10%
3N~ 380V ± 10%
DEGREE OF PROTECTION
IP40
IP44
IP40
IP44
EQUIPMENT
LMO44
LMO44
LMO44
LMO44
FLAME DETECTOR
Photoresistor
Photoresistor
Photoresistor
Photoresistor
AIR FLOW REGULATION
hydraulic jack
electric servomotor
hydraulic jack
electric servomotor
SOUND PRESSURE**
dBA
76
76
75
75
SOUND POWER***
dBA
76
76
75
75
WEIGHT WITH PACKING
kg
34
34
36
36
WEIGHT WITHOUT PACKING
kg
34
34
36
36
Lower calorific power:
Diesel oil: Hi = 11.86 kWh/kg = 42.70 Mj/kg
* Total absorption at start with ignition transformer on.
The measurement has been carried out in Baltur's laboratory, in accordance with EN 150361 standard.
** Acoustic pressure measured one meter behind the equipment, with burner operating at maximum rated heat input, it refers to
Baltur's laboratory environment conditions and cannot be compared to measurements carried out in different locations.
*** Acoustic pressure was obtained characterizing Baltur's laboratory with a sample source, this measurement has an accuracy
of class 2 (engineering class) with a standard deviation f 1.5 dB(A).
ENGLISH
5 / 36
0006081323_201504
Summary of Contents for TBL 45P
Page 2: ......
Page 33: ...SCHEMI ELETTRICI ITALIANO 31 36 0006081323_201504...
Page 34: ...ITALIANO 32 36 0006081323_201504...
Page 35: ...ITALIANO 33 36 0006081323_201504...
Page 36: ...ITALIANO 34 36 0006081323_201504...
Page 38: ...ITALIANO 36 36 0006081323_201504...
Page 69: ...WIRING DIAGRAMS ENGLISH 31 36 0006081323_201504...
Page 70: ...ENGLISH 32 36 0006081323_201504...
Page 71: ...ENGLISH 33 36 0006081323_201504...
Page 72: ...ENGLISH 34 36 0006081323_201504...
Page 74: ...ENGLISH 36 36 0006081323_201504...
Page 75: ......