NATURAL GAS IGNITION AND REGULATION
•
Check that there is water in the boiler and that the gate valves of
the system are open.
•
Make sure that the combustion products may be freely vented
through the boiler and flue dampers.
• Make sure that the mains voltage corresponds to the manufactu-
rer's requirements and that all electrical connections made at the
installation site are effected properly as illustrated in our wiring dia
-
gram.
•
Prevent the second flame from operating by disconnecting the
4-pole connector 4-pole connector from the electrical panel for
TBG 45P-60P burners;
•
Prevent the second flame from operating by disconnecting the
4-pole connector 4-pole connector from the electrical panel for
TBG 45P-60P burners;
•
Adjust the air for the ignition flame:
-
for TBG 45P - 60P burners with an electric servomotor, follow
the instructions provided in the SERVOMOTOR CAM ADJUST-
MENT drawing;
-
for TBG 45P - 60P burners with an electric servomotor, follow
the instructions provided in the SERVOMOTOR CAM ADJUST-
MENT drawing;
•
Open the combustion air regulator as necessary and open approx.
a third of the passage of air between flame disk and head (diffu
-
ser). Act on the regulators incorporated in the safety and operating
valve in such a way as to obtain the gas delivery deemed to be
necessary.
•
On models with a three-phase power supply, with the I/O switch
START/STOP switch on the burner panel in position “O” and the
general switch enabled, check by closing the contactor by hand
that the motor revolves in the correct direction.
•
If necessary, invert the two cables of the line powering the motor for
reversing the rotation direction.
•
Now turn on the burner panel switch START/STOP switch. The
control equipment is powered and the programmer activates the
burner as described in the chapter “Operation description”. During
pre-ventilation, make sure that the air pressure switch changes its
status. If the air pressure switch does not detect sufficient pressure,
the ignition transformer is not switched on, nor are the gas valves,
therefore the equipment “locks out”.
•
During the first ignition several “lock outs” may occur due to the
following reasons:
•
With the burner on at minimum you must carry out an immediate
visual check on the extent of and appearance of the flame, perfor
-
ming the necessary corrections with the gas and air supply regu
-
lators (see points 4 and 5). Subsequently a check is carried out on
the quantity of gas supplied, by reading the meter. If necessary the
gas supply and the corresponding combustion air can be corrected
as previously described (points 4 and 5). Then check the combu
-
stion with the suitable instruments. For a correct air/gas ratio you
must find a carbon dioxide (CO2) value for natural gas that is at
least 8 % or O2 = 6% at minimum burner supply up to an optimal
value of 10 % or O2 = 3% for maximum supply. It is essential to
check, with a suitable instrument, that the percentage of carbon
monoxide (CO) present in the fumes does not exceed the limit set
by regulations at the time of installation.
•
Repeatedly check that the first flame is properly supplied. After
adjusting operation with the first flame, turn off the burner, open the
main switch and close the electrical circuit commanding inclusion
of the second flame, reconnect the previously disconnected 4-pole
connector for burners TBG 45P-60P.
•
Repeatedly check that the first flame is properly supplied. After
adjusting operation with the first flame, turn off the burner, open
the main switch and close the electrical circuit commanding inclu
-
sion of the second flame, reconnect the wire to terminal 5 on the
terminal board on the printed circuit powering coil Y2 for burners
TBG 45-60.
0002935620
2
8
7
1
5
10
6
9
4
3
ENGLISH
15 / 34
0006160178_202002
Summary of Contents for TBG 45 P
Page 2: ......
Page 33: ...SCHEMI ELETTRICI ITALIANO 31 34 0006160178_202002...
Page 34: ...ITALIANO 32 34 0006160178_202002...
Page 36: ...ITALIANO 34 34 0006160178_202002...
Page 67: ...WIRING DIAGRAMS ENGLISH 31 34 0006160178_202002...
Page 68: ...ENGLISH 32 34 0006160178_202002...
Page 70: ...ENGLISH 34 34 0006160178_202002...
Page 71: ......